Q1 | Purpose of the Electricians Act

Which of the following is the purpose of the Electricians Act (電気工事士法)?

  1. To regulate the manufacture and sale of electrical appliances and prevent hazards caused by them
  2. To register electrical contractors and ensure that their business is carried out properly
  3. To set the qualifications and duties of people who do electrical work, and prevent disasters caused by defective electrical work
  4. To regulate the construction, maintenance and operation of electrical facilities to secure public safety and protect the environment
AnswerC. To set the qualifications and duties of people who do electrical work, and prevent disasters caused by defective electrical work

Article 1 of the Electricians Act says its purpose is to set the qualifications and duties of people engaged in electrical work, and so help prevent disasters caused by defective electrical work. Regulating the manufacture and sale of appliances is the purpose of the Electrical Appliances and Materials Safety Act (電気用品安全法). Registering contractors and making their business proper is the purpose of the Electrical Contractors Act (電気工事業法). Regulating the construction, maintenance and operation of electrical facilities belongs to the Electricity Business Act (電気事業法).

Q2 | Scope of a second-class electrician

Under the Electricians Act, which electrical work may a person holding only a second-class electrician licence do?

  1. Low-voltage wiring work in a factory (private-use) with a maximum demand of 300 kW
  2. Work on a 20 kW solar power system installed at a shop that receives power at low voltage
  3. Neon work for a neon sign installed on the roof of a building
  4. Work on the emergency standby generator of a building with a maximum demand of 400 kW
AnswerB. Work on a 20 kW solar power system installed at a shop that receives power at low voltage

A second-class electrician may work on general electrical facilities etc. (一般用電気工作物等), which include general electrical facilities and small business-use electrical facilities (小規模事業用電気工作物). A 20 kW solar system is a small business-use facility, so it is within the second-class scope. A 300 kW factory is a private-use electrical facility (自家用電気工作物) under the Act, which needs a first-class electrician (or a certified electrical worker (認定電気工事従事者) for parts used at 600 V or below). Neon work and emergency standby generator work are special electrical work (特殊電気工事) and need a special electrical work qualification (特種電気工事資格者).

Q3 | Minor work

Which of the following is "minor work" (軽微な工事) under the Order for Enforcement of the Electricians Act, so that it may be done without an electrician licence?

  1. Putting wires into a synthetic-resin flexible conduit
  2. Mounting a flush-type outlet in a wall box
  3. Burying an earth electrode in the ground and connecting the earthing wire
  4. Wiring the secondary side of a small transformer (secondary voltage 24 V) for an intercom
AnswerD. Wiring the secondary side of a small transformer (secondary voltage 24 V) for an intercom

Article 1 of the Order treats wiring on the secondary side of a small transformer for a bell or intercom (secondary voltage 36 V or less) as minor work. 24 V is 36 V or less, so no licence is needed. Putting wires into conduit, attaching wiring devices to building materials (except replacing exposed switches or outlets), and burying an earth electrode and connecting the earthing wire are all listed in Article 2 of the Enforcement Regulations as work that only an electrician may do.

Q4 | Work that needs a licence

In work on general electrical facilities etc., which task may only be done by a licensed electrician?

  1. Fixing a metal box to a building material
  2. Replacing an exposed-type outlet with one of the same type
  3. Installing an electricity meter used at 600 V or below
  4. Assisting an electrician who is joining wires
AnswerA. Fixing a metal box to a building material

Article 2 of the Enforcement Regulations lists fixing a metal box to a building material as work only an electrician may do. Replacing an exposed-type switch or outlet is excluded from the work that needs a licence. Installing an electricity meter used at 600 V or below is minor work (軽微な工事) under Article 1 of the Order. Assisting work done by an electrician is minor work (軽微な作業) under Article 2 of the Regulations.

Q5 | Certified electrical worker

Which is "simple electrical work" (簡易電気工事) that a holder of a certified electrical worker certificate (認定電気工事従事者認定証) may do?

  1. Work on the high-voltage receiving equipment of a building with a maximum demand under 500 kW
  2. Work on the emergency standby generator of a private-use electrical facility
  3. Work on equipment used at 600 V or below in a factory with a maximum demand under 500 kW (excluding power lines)
  4. Work on equipment used at 600 V or below in a factory with a maximum demand of 500 kW or more
AnswerC. Work on equipment used at 600 V or below in a factory with a maximum demand under 500 kW (excluding power lines)

Simple electrical work is work on private-use electrical facilities under the Electricians Act (such as demand facilities under 500 kW) that are used at 600 V or below, excluding power lines (Article 2-3 of the Enforcement Regulations). Work on high-voltage receiving equipment belongs to a first-class electrician. Emergency standby generator work is special electrical work and needs a special electrical work qualification. Demand facilities of 500 kW or more are outside the private-use facilities covered by the Electricians Act, so the work is not simple electrical work either.

Q6 | Special electrical work

Which electrical work may only be done by a holder of a special electrical work qualification (特種電気工事資格者)?

  1. Replacing the distribution board of an ordinary house
  2. Work on the emergency standby generator of a private-use electrical facility
  3. Work on lighting used at 600 V or below in a private-use electrical facility
  4. Work on an 8 kW solar power system at a house that receives power at low voltage
AnswerB. Work on the emergency standby generator of a private-use electrical facility

Special electrical work (特殊電気工事) means two kinds of work: neon work and emergency standby generator work (Article 2-2 of the Enforcement Regulations). Even a first-class electrician cannot do them without a special qualification certificate for that kind of work. Replacing a house's distribution board is work on a general electrical facility, which first- and second-class electricians may do. Lighting used at 600 V or below in a private-use facility is simple electrical work, which a first-class electrician or a certified electrical worker may do. An 8 kW solar system is a general electrical facility, which a second-class electrician may do.

Q7 | Duties of an electrician

Which of the following is a duty of a second-class electrician under the Electricians Act?

  1. To take a periodic training course within every 5 years from the date the licence was issued
  2. To report the details of each electrical job to the prefectural governor
  3. To apply for the licence to be rewritten when your address changes
  4. To carry the electrician licence while doing electrical work
AnswerD. To carry the electrician licence while doing electrical work

Article 5 of the Electricians Act requires an electrician to do the work so that it meets the technical standards, and to carry the licence while working. The periodic training course within every 5 years is a duty of first-class electricians (Article 4-3), not second-class ones. There is no duty to report each job to the governor. The licence does not show your address, so a change of address does not require rewriting it.

Q8 | Rewriting a licence

A second-class electrician has changed their name. Where should they apply to have the licence rewritten?

  1. The governor of the prefecture that issued the licence
  2. The governor of the prefecture where they now live
  3. The Minister of Economy, Trade and Industry
  4. The Electrical Engineers Examination Center
AnswerA. The governor of the prefecture that issued the licence

Under Article 5 of the Order for Enforcement of the Electricians Act, when an item on the licence (such as the name) changes, you apply for rewriting to the governor of the prefecture that issued the licence, not the governor where you now live. Licences are issued by prefectural governors, so the Minister of Economy, Trade and Industry is not where you apply. The Electrical Engineers Examination Center (電気技術者試験センター) runs the examination; it does not handle licence procedures.

Q9 | Finding a lost licence

After losing your licence and getting it reissued, you find the lost licence. What must you do?

  1. Both are valid, so you may carry either one
  2. You only need to destroy the found licence yourself
  3. Submit it without delay to the prefectural governor who reissued the licence
  4. Return it without delay to the Minister of Economy, Trade and Industry
AnswerC. Submit it without delay to the prefectural governor who reissued the licence

Under Article 4(3) of the Order for Enforcement of the Electricians Act, a person who lost a licence, got it reissued, and then finds the lost one must submit it without delay to the prefectural governor who reissued it. You cannot keep using both, and destroying it yourself is not enough. It goes to the governor who reissued it, not to the Minister.

Q10 | Requests for reports

Under the Electricians Act, who may require an electrician to report on their electrical work?

  1. The Minister of Economy, Trade and Industry
  2. The prefectural governor
  3. The power line operator (電線路維持運用者)
  4. The mayor of the city, town or village
AnswerB. The prefectural governor

Under Article 9 of the Electricians Act, the prefectural governor may, to the extent needed to enforce the Act, require electricians, special electrical work qualification holders and certified electrical workers to report on their electrical work. The Minister and the mayor are not the parties named in this article. The power line operator investigates general electrical facilities under the Electricity Business Act (電気事業法); it does not collect reports from electricians.

Q11 | Low voltage for AC

Under the Ministerial Ordinance on Technical Standards for Electrical Equipment (電気設備に関する技術基準を定める省令), what is the range of "low voltage" (低圧) for AC?

  1. 300 V or less
  2. 600 V or less
  3. 750 V or less
  4. 7,000 V or less
AnswerB. 600 V or less

Under Article 2 of the Ordinance, low voltage is 750 V or less for DC and 600 V or less for AC. Voltages of 300 V or less are low voltage too, but 300 V is not the upper limit. 750 V or less is the low-voltage range for DC. 7,000 V is the upper limit of high voltage: for AC, over 600 V up to 7,000 V is high voltage.

Q12 | Matching voltage and class

Which pair of voltage and class under the Technical Standards Ordinance is correct?

  1. AC 400 V: high voltage
  2. AC 6,600 V: extra-high voltage
  3. DC 10,000 V: high voltage
  4. DC 700 V: low voltage
AnswerD. DC 700 V: low voltage

For DC, 750 V or less is low voltage, so DC 700 V is low voltage. AC 400 V is 600 V or less, so it is low voltage, not high voltage. AC 6,600 V is over 600 V and up to 7,000 V, so it is high voltage. DC 10,000 V is over 7,000 V, so it is extra-high voltage.

Q13 | General electrical facilities

Which of the following is a general electrical facility (一般用電気工作物) under the Electricity Business Act (電気事業法)?

  1. The indoor wiring of a house that receives power at low voltage, plus a 5 kW solar system on the same premises
  2. The receiving equipment and indoor wiring of a factory that receives power at a high voltage of 6,600 V
  3. A 30 kW solar system installed, with no other generators, at a shop that receives power at low voltage
  4. The electrical equipment of a site that manufactures explosives (not fireworks) and receives power at low voltage
AnswerA. The indoor wiring of a house that receives power at low voltage, plus a 5 kW solar system on the same premises

General electrical facilities are equipment that receives power at 600 V or below and uses it on the same premises, plus small generators. A solar system under 10 kW is general, so a 5 kW solar system and the house wiring are general electrical facilities. A factory that receives high voltage is a private-use electrical facility (自家用電気工作物). A 30 kW solar system is 10 kW or more and under 50 kW, so it is a small business-use electrical facility (小規模事業用電気工作物). Sites that manufacture explosives are excluded from general electrical facilities by Article 48 of the Enforcement Regulations.

Q14 | Small business-use electrical facilities

Only one of the following generators is installed on premises that receive power at low voltage. Which is a small business-use electrical facility (小規模事業用電気工作物)?

  1. An 8 kW solar power system
  2. A 5 kW fuel cell power system
  3. A 3 kW wind power system
  4. A 60 kW solar power system
AnswerC. A 3 kW wind power system

No wind power system counts as a general electrical facility (the limit in Article 48(4) of the Enforcement Regulations is 0 kW), and small wind generators under 20 kW are small business-use electrical facilities. So a 3 kW wind system is small business-use. An 8 kW solar system (under 10 kW) and a 5 kW fuel cell (under 10 kW) are general electrical facilities. A 60 kW solar system is 50 kW or more, so it is not a small generator and not a small business-use facility.

Q15 | Inspection of general electrical facilities

Which statement about checking whether general electrical facilities meet the technical standards is correct?

  1. The owner checks them every year and reports the results to the prefectural governor
  2. The electrician who did the work checks them at least once every 3 years
  3. The prefectural governor enters and checks them at least once every 10 years
  4. The power line operator checks them, as a rule at least once every 4 years
AnswerD. The power line operator checks them, as a rule at least once every 4 years

Under Article 57 of the Electricity Business Act, the person who maintains and operates the power line directly connected to the general electrical facility (the power line operator, 電線路維持運用者) does the investigation. Under Article 96 of the Enforcement Regulations, periodic checks are at least once every 4 years (at least once every 5 years for facilities whose inspection has been entrusted by the owner to a registered inspection contractor (登録点検業務受託法人)), and a check is also made when installation or alteration work is completed. Owners, electricians and governors have no such duty.

Q16 | When a facility does not comply

A power line operator's investigation finds that a general electrical facility does not meet the technical standards. What does the Electricity Business Act require?

  1. Without delay, tell the owner or occupier the needed measures and the result of not taking them
  2. Stop supplying power to the facility at once and not restart supply until repairs are finished
  3. Report to the Minister of Economy, Trade and Industry and ask for a fine on the owner
  4. Order the electrician who did the work to repair it at their own expense
AnswerA. Without delay, tell the owner or occupier the needed measures and the result of not taking them

Under Article 57(2) of the Electricity Business Act, the power line operator must notify the owner or occupier without delay of the measures needed to meet the technical standards and of the consequences if those measures are not taken. The article does not provide for stopping the supply, for fines through a report to the Minister, or for ordering the electrician to make repairs.

Q17 | Work that needs a first-class licence

Under the Electricians Act, which electrical work needs a first-class electrician licence (excluding special electrical work)?

  1. Indoor wiring of an ordinary house that receives power at low voltage
  2. Work on the high-voltage receiving equipment of a building with a maximum demand of 400 kW
  3. Work on the demand facilities of a factory with a maximum demand of 1,000 kW
  4. Work on a 20 kW solar system at a shop that receives power at low voltage
AnswerB. Work on the high-voltage receiving equipment of a building with a maximum demand of 400 kW

Private-use electrical facilities under the Electricians Act are demand facilities under 500 kW and similar, and work on them belongs to first-class electricians (certified electrical workers may also work on parts used at 600 V or below). High-voltage receiving equipment in a 400 kW building is such a facility. An ordinary house and a 20 kW solar system (small business-use) are general electrical facilities etc., which second-class electricians may also work on. Demand facilities of 500 kW or more are excluded from the Act's private-use facilities, so the Act's licences do not cover them.

Q18 | Where to register an electrical contracting business

A company wants to run an electrical contracting business that includes general electrical work, with offices in Tokyo and Kanagawa. Where must it register?

  1. The governor of Tokyo, where the head office is
  2. Both the governor of Tokyo and the governor of Kanagawa
  3. The Minister of Economy, Trade and Industry
  4. The mayor of each city or ward where an office is located
AnswerC. The Minister of Economy, Trade and Industry

Under Article 3 of the Electrical Contractors Act (電気工事業法), a business with offices in two or more prefectures registers with the Minister of Economy, Trade and Industry. A business with offices in only one prefecture registers with that prefecture's governor. It does not register only with the governor of the head office's prefecture, or with both governors. Mayors are not registration authorities.

Q19 | Chief electrician

Who may be appointed as the chief electrician (主任電気工事士) at an office of a registered electrical contractor that does general electrical work?

  1. A second-class electrician with at least 1 year of work experience after the licence was issued
  2. A person who holds a certified electrical worker certificate
  3. A second-class electrician with at least 3 years of work experience after the licence was issued
  4. A person with no electrician licence but at least 10 years of work experience
AnswerC. A second-class electrician with at least 3 years of work experience after the licence was issued

Under Article 19 of the Electrical Contractors Act, a chief electrician must be a first-class electrician, or a second-class electrician with at least 3 years of electrical work experience after the licence was issued. One year of experience is not enough. A certified electrical worker does not meet the requirement. A person with no licence cannot be appointed, however long their experience.

Q20 | Instruments to keep at an office

Which set of instruments must, under the Electrical Contractors Act, be kept at an office that does only general electrical work?

  1. Insulation resistance tester, earth resistance tester, and a multimeter (回路計) that measures resistance and AC voltage
  2. Insulation resistance tester, earth resistance tester, and a high-voltage detector
  3. Multimeter, protective relay tester, and dielectric withstand tester
  4. Insulation resistance tester, clamp meter, and phase rotation tester
AnswerA. Insulation resistance tester, earth resistance tester, and a multimeter (回路計) that measures resistance and AC voltage

Under Article 24 of the Act and Article 11 of its Enforcement Regulations, an office doing only general electrical work must keep an insulation resistance tester, an earth resistance tester, and a multimeter that can measure resistance and AC voltage. A high-voltage detector, a protective relay tester and a dielectric withstand tester are extra instruments for offices that also do private-use electrical work. A clamp meter and a phase rotation tester are not among the instruments the regulation requires.

Q21 | Record books

Which statement about the record books (帳簿) of a registered electrical contractor is correct?

  1. One book at the head office is enough; each office does not need one
  2. The books must be kept for 3 years from the date of entry
  3. Wiring diagrams and inspection results need not be recorded
  4. Each office keeps a book, and it is kept for 5 years from the date of entry
AnswerD. Each office keeps a book, and it is kept for 5 years from the date of entry

Under Article 26 of the Electrical Contractors Act, a book is kept at each office, and under Article 13 of the Enforcement Regulations it is kept for 5 years from the date of entry. The entries include the client's name and address, the type and site of the work, the date, the names of the chief electrician and the workers, the wiring diagram, and the inspection results. One book at the head office, 3 years, and leaving out diagrams and results all differ from the rules.

Q22 | Displaying a sign

Which statement about the sign (標識) of a registered electrical contractor is correct?

  1. It only needs to be displayed in a visible place at the head office
  2. It is displayed at each office and work site (except sites where work ends within one day)
  3. It only needs to be displayed at the work sites while the work is going on
  4. It is displayed where it can be easily seen from outside the representative's home
AnswerB. It is displayed at each office and work site (except sites where work ends within one day)

Under Article 25 of the Electrical Contractors Act, the sign is displayed in an easily visible place at each office and at each site of electrical work. Under Article 12 of the Enforcement Regulations, sites where the electrical work is completed in one day are excluded. Head office only, work sites only, and the representative's home all differ from the rules.

Q23 | Examples of specified electrical appliances

Which of the following is a specified electrical appliance (特定電気用品) under the Electrical Appliances and Materials Safety Act (電気用品安全法)?

  1. Synthetic-resin flexible conduit for indoor wiring (PF pipe, 合成樹脂製可とう電線管)
  2. VVF cable (conductor diameter 2.0 mm, 3 cores)
  3. A ceiling-recessed ventilation fan rated at 30 W
  4. A ceiling-mounted LED lighting fixture rated at 20 W
AnswerB. VVF cable (conductor diameter 2.0 mm, 3 cores)

In METI's list of covered items, cables with a conductor cross-section of 22 mm² or less, 7 cores or fewer, and a rubber or synthetic-resin sheath are specified electrical appliances. A 2.0 mm diameter conductor has a cross-section of about 3.1 mm², so this VVF cable (600 V PVC-insulated PVC-sheathed flat cable) qualifies. Synthetic-resin flexible conduit, ventilation fans (rated 300 W or less) and LED lighting fixtures are non-specified electrical appliances.

Q24 | Appliances that may be used in work

Under the Electrical Appliances and Materials Safety Act, which statement about an electrician using electrical appliances in house wiring work is correct?

  1. Appliances without the mark required by the Act must not be used in electrical work
  2. The marking rules apply only when selling; using appliances in work is not restricted
  3. Fittings you made yourself may be used in work even without the mark
  4. Specified appliances are already inspected, so they may be used even without the mark
AnswerA. Appliances without the mark required by the Act must not be used in electrical work

Under Article 28 of the Act, electricians and others must not use electrical appliances in installing or altering electrical facilities unless they bear the mark in Article 10(1). This use restriction exists separately from the sales restriction (Article 27). Self-made fittings without the mark may not be used. Specified appliances also may not be used unless they bear the mark.

Q25 | Marking of specified appliances

Which item must appear in the marking of a specified electrical appliance but is not required for a non-specified appliance?

  1. The name of the notified business operator (届出事業者)
  2. The symbol set by the regulations (PSE mark)
  3. The name of the shop that sold the appliance
  4. The name of the registered inspection body that inspected it
AnswerD. The name of the registered inspection body that inspected it

Under Article 17 of the Enforcement Regulations, the marking of a specified appliance consists of the symbol (PSE in a diamond), the name of the notified business operator, and the name of the registered inspection body that issued the conformity certificate. A non-specified appliance shows the symbol (PSE in a circle) and the operator's name; the inspection body's name is not required. The operator's name and the PSE symbol are needed for both. The name of the shop is not part of the marking.

Practice: answer the questions on this page

This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.

* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.