Q1 | When general-use electrical facilities are inspected
For general-use electrical facilities (一般用電気工作物) such as houses, which timing matches the basic rule in the Ordinance for Enforcement of the Electricity Business Act (電気事業法施行規則) for the "investigation" of conformity with technical standards (when no registered inspection-service corporation has been entrusted)?
At installation and at completion of alteration work, and at least once every 4 years
Only at installation, and afterwards only when the owner asks
At installation and at completion of alteration work, and at least once every 10 years
Not at installation, but regularly once every year
AnswerA. At installation and at completion of alteration work, and at least once every 4 years
Article 96 of the Ordinance requires the investigation at installation and when alteration work is completed, plus at least once every 4 years as a rule (once every 5 years when a registered inspection-service corporation is entrusted; as of October 2026). "Only at installation", "every 10 years" and "not at installation" do not match the text.
Q2 | Order of a completion inspection
Which is the most appropriate order for a completion inspection (竣工検査) of general-use electrical facilities?
Energizing test → visual check → measurements and tests
Measurements and tests → energizing test → visual check
Visual check → measurements and tests → energizing test
Visual check → energizing test → measurements and tests
AnswerC. Visual check → measurements and tests → energizing test
First check the work visually, then measure insulation resistance, earth resistance and continuity with the power off, and only when no fault is found apply power (energizing test). Doing the energizing test earlier could cause electric shock, fire or damage if there is a wiring error or poor insulation, so the other three orders are not appropriate.
Q3 | Insulation resistance: single-phase 3-wire
A 200 V branch circuit is supplied from a single-phase 3-wire 100/200 V system. What is the minimum insulation resistance between the circuit and earth set by the Ministerial Ordinance on Technical Standards for Electrical Equipment (電気設備に関する技術基準を定める省令)?
0.2 MΩ
0.1 MΩ
0.4 MΩ
1 MΩ
AnswerB. 0.1 MΩ
In a single-phase 3-wire 100/200 V system, the voltage between each wire and earth (voltage to earth, 対地電圧) is 100 V even for a 200 V circuit. Since the circuit is 300 V or less with a voltage to earth of 150 V or less, the minimum is 0.1 MΩ. 0.2 MΩ is for circuits of 300 V or less with more than 150 V to earth (such as three-phase 3-wire 200 V), and 0.4 MΩ is for circuits over 300 V. 1 MΩ is not a value in the Ordinance.
Q4 | Insulation resistance: three-phase 200 V
For a branch circuit of a three-phase 3-wire 200 V motor, which is the correct minimum insulation resistance between the circuit and earth?
0.1 MΩ
0.4 MΩ
1 MΩ
0.2 MΩ
AnswerD. 0.2 MΩ
A three-phase 3-wire 200 V circuit is 300 V or less, but its voltage to earth exceeds 150 V, so Article 58 of the Ordinance requires at least 0.2 MΩ. 0.1 MΩ applies when the voltage to earth is 150 V or less, and 0.4 MΩ applies when the circuit voltage exceeds 300 V. 1 MΩ is not a value in the Ordinance.
Q5 | Insulation resistance: over 300 V
For a 400 V three-phase motor circuit, which is the correct minimum insulation resistance between the circuit and earth?
0.4 MΩ
0.2 MΩ
0.1 MΩ
1 MΩ
AnswerA. 0.4 MΩ
Article 58 of the Ordinance requires at least 0.4 MΩ for low-voltage circuits whose voltage exceeds 300 V. 0.2 MΩ and 0.1 MΩ are for circuits of 300 V or less, so they do not apply to a 400 V circuit. 1 MΩ is not a value in the Ordinance.
Q6 | Judging by leakage current
When it is difficult to measure insulation resistance on a low-voltage circuit (for example, the power cannot be cut), the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈) accepts the circuit if the leakage current with the operating voltage applied is at most how much?
0.1 mA
0.5 mA
1 mA
10 mA
AnswerC. 1 mA
Article 14 of the Interpretation says that when insulation resistance is hard to measure, the leakage current with the operating voltage applied must be 1 mA or less. With 100 V to earth and 0.1 MΩ, 100 ÷ 100,000 = 0.001 A = 1 mA, which matches the insulation resistance limit. 0.1 mA and 0.5 mA are stricter than the rule, and 10 mA is larger than the rule, so they are wrong.
Q7 | Insulation resistance from leakage current
On a circuit with 100 V to earth, the leakage current between the circuit and earth was measured as 0.5 mA. What is the insulation resistance between the circuit and earth?
0.1 MΩ
0.2 MΩ
0.5 MΩ
2 MΩ
AnswerB. 0.2 MΩ
Use Ohm's law, R = V ÷ I. 0.5 mA = 0.0005 A, so R = 100 ÷ 0.0005 = 200,000 Ω = 0.2 MΩ. 0.1 MΩ would correspond to 1 mA, 0.5 MΩ to 0.2 mA, and 2 MΩ to 0.05 mA; these come from unit-conversion mistakes.
Q8 | How an insulation resistance tester works
Which statement about an insulation resistance tester (絶縁抵抗計, "megger") is correct?
It applies 100 V AC and finds the resistance from the current
As a rule, it is used while the circuit is energized
The resistance range of a circuit tester can measure the same value instead
It applies a high DC voltage, so electronic devices are disconnected first
AnswerD. It applies a high DC voltage, so electronic devices are disconnected first
An insulation resistance tester applies a high DC voltage and calculates the insulation resistance from the tiny current. Electronic devices left connected can be damaged, so they are disconnected first. It does not apply 100 V AC. Insulation resistance is measured with the power off. A circuit tester's resistance range uses a low voltage and is not used for megohm-level insulation measurement.
Q9 | Measuring between conductors
To measure the insulation resistance between the conductors of a lighting circuit, which preparation is the most appropriate?
Open the branch switch, remove loads such as lamps, and keep the wall switch ON
Open the branch switch, keep loads connected, and keep the wall switch ON
Keep the branch switch closed, remove loads, and keep the wall switch OFF
Open the branch switch, remove loads, and keep the wall switch OFF
AnswerA. Open the branch switch, remove loads such as lamps, and keep the wall switch ON
Between conductors, turn off the power (open the branch switch) and remove the loads. If loads stay connected, you measure the load itself (such as a lamp filament) and get a very small value. Keep the wall switch (点滅器) ON so the wiring beyond it is included. Measuring with the branch switch closed is dangerous, and with the wall switch OFF the wiring beyond it is not measured.
Q10 | Measuring between the circuit and earth
Which is the most appropriate way to measure the insulation resistance between a lighting circuit and earth?
Keep the branch switch closed and energized, and measure between the live wire and earth
Open the branch switch and the wall switch, and measure only the grounded wire to earth
Open the branch switch, keep loads connected, turn the wall switch ON, and measure all wires together to earth
Open the branch switch; it cannot be measured to earth unless all loads are removed
AnswerC. Open the branch switch, keep loads connected, turn the wall switch ON, and measure all wires together to earth
Between the circuit and earth, open the branch switch to cut the power, turn the wall switch ON, and measure all wires together against earth. The load sits between the wires, not between the wires and earth, so loads may stay connected. Measuring while energized is dangerous. Measuring only the grounded wire, or with the wall switch OFF, leaves parts unmeasured.
Q11 | Class D grounding resistance
Grounding is applied to the metal frame of a 200 V three-phase motor. No device that automatically breaks the circuit on a ground fault is installed. Which upper limit of earth resistance matches the Interpretation of the Technical Standards?
10 Ω or less
100 Ω or less
500 Ω or less
1000 Ω or less
AnswerB. 100 Ω or less
Frames of equipment of 300 V or less need Class D grounding (D種接地工事, Article 29), whose earth resistance must be 100 Ω or less (Article 17). 10 Ω is the Class C value, and 500 Ω applies only when a device breaks the circuit within 0.5 s. 1000 Ω is not a value for any class.
Q12 | Judgment with an earth-leakage breaker
Class D grounding was applied to the frame of a 200 V device in a wet location. The circuit has an earth-leakage circuit breaker (漏電遮断器) with a rated sensitivity of 30 mA and an operating time of 0.1 s. The measured earth resistance was 350 Ω. Which judgment is correct?
It fails because it exceeds 100 Ω
With a breaker it becomes Class C grounding, which needs 10 Ω or less, so it fails
With a breaker no grounding is needed, so no judgment is necessary
With a device that breaks within 0.5 s, 500 Ω or less is allowed, so it passes
AnswerD. With a device that breaks within 0.5 s, 500 Ω or less is allowed, so it passes
Class D grounding is 100 Ω or less as a rule, but 500 Ω or less is allowed when a device automatically breaks the circuit within 0.5 s on a ground fault (Article 17), so 350 Ω passes. A breaker does not change it into Class C. Grounding may be omitted only with a current-operated breaker of 15 mA or less and 0.1 s or less in a place that is not wet (Article 29), so it cannot be omitted here.
Q13 | Grounding of equipment over 300 V
Which combination of grounding class and earth resistance is correct for the metal frame of a 400 V three-phase motor? No device that automatically breaks the circuit within 0.5 s on a ground fault is installed.
Class D, 100 Ω or less
Class D, 500 Ω or less
Class C, 10 Ω or less
Class C, 100 Ω or less
AnswerC. Class C, 10 Ω or less
Frames of low-voltage equipment over 300 V need Class C grounding (C種接地工事, Article 29), with an earth resistance of 10 Ω or less (Article 17). Class D is for equipment of 300 V or less. 500 Ω applies only with an automatic breaking device within 0.5 s, which is not the case here. The basic Class C value is not 100 Ω.
Q14 | When grounding may be omitted
Which case matches the Interpretation of the Technical Standards as one where Class D grounding of the metal frame of low-voltage equipment may be omitted?
Equipment with 100 V AC to earth installed in a dry place
Equipment with 200 V AC to earth installed in a wet place
An earth-leakage breaker of 30 mA and 0.1 s on the circuit of equipment in a wet place
Equipment of 400 V installed in a dry place
AnswerA. Equipment with 100 V AC to earth installed in a dry place
Article 29, paragraph 2 of the Interpretation allows omission when, for example, equipment with 150 V AC or less to earth is installed in a dry place. 200 V to earth in a wet place does not qualify. Omission with a breaker needs a current-operated breaker of 15 mA or less and 0.1 s or less in a place that is not wet. 400 V equipment needs Class C grounding, and being in a dry place alone does not allow omission (as of October 2026).
Q15 | Auxiliary electrodes of an earth tester
When measuring earth resistance with an earth resistance tester, which arrangement of the electrode under test E and the auxiliary electrodes P and C is the most appropriate?
Put E in the center with P and C on either side
Drive P and C into the same spot
Drive P and C within 1 m of E
Line up E, P and C almost in a straight line with P in the middle
AnswerD. Line up E, P and C almost in a straight line with P in the middle
An earth resistance tester sends current through C and measures voltage at P to find the resistance of E. So E, P and C are placed almost in a straight line with P in the middle, spaced as the manual says (often about 10 m each). Putting E in the center, putting P and C in the same spot, or driving them right next to E will not give a correct value.
Q16 | Use of a voltage detector
Which is the correct use of a low-voltage detector (検電器)?
To measure the insulation resistance of wires
To check whether a circuit is live (energized)
To measure the earth resistance of an earth electrode
To check the phase sequence of three-phase AC
AnswerB. To check whether a circuit is live (energized)
A voltage detector checks whether voltage is present on a circuit (whether it is live), for example as a safety check before work. Insulation resistance is measured with an insulation resistance tester, earth resistance with an earth resistance tester, and phase sequence with a phase sequence indicator (検相器).
Q17 | Instrument for a continuity test
Which instrument is the most appropriate for a continuity test (導通試験), which checks that wiring is not broken and is connected correctly?
Circuit tester (multimeter)
Illuminance meter
Phase sequence indicator
Earth resistance tester
AnswerA. Circuit tester (multimeter)
In a continuity test, the resistance range of a circuit tester (回路計) is used to check that current can pass between the two ends of a wire. An illuminance meter measures brightness, a phase sequence indicator checks three-phase phase order, and an earth resistance tester measures resistance between an electrode and earth; none checks wiring continuity.
Q18 | Measuring leakage with a clamp meter
When measuring the leakage current of a single-phase 3-wire circuit with a clamp meter (クランプ形電流計), which wires should be clamped?
Only the neutral wire
Only one of the live wires
All three wires, neutral and live, together
Only the two live wires together
AnswerC. All three wires, neutral and live, together
When all the wires of the circuit are clamped together, outgoing and returning currents cancel to zero if there is no leakage, and what remains is shown as leakage current. For single-phase 3-wire, that means all three wires. Clamping one wire measures load current, and clamping only the two live wires leaves the neutral current uncancelled.
Q19 | Use of a phase sequence indicator
After installing a three-phase induction motor, you want to check the phase sequence of the three-phase supply, which affects the direction of rotation. Which instrument is correct?
Circuit tester
Illuminance meter
Clamp meter
Phase sequence indicator
AnswerD. Phase sequence indicator
The phase sequence of three-phase AC (the order in which each phase reaches its peak) is checked with a phase sequence indicator (検相器). If it is reversed, the motor turns the other way. A circuit tester measures resistance and voltage, an illuminance meter measures brightness, and a clamp meter measures current; none shows the phase sequence.
Q20 | Instruments an office must keep
Under the Ordinance for Enforcement of the Act on Regulation of Electrical Construction Business (電気工事業の業務の適正化に関する法律施行規則), which set of instruments must an office that handles only general-use electrical work keep?
Article 11 of the Ordinance says such an office must keep an insulation resistance tester, an earth resistance tester, and a circuit tester that can measure resistance and AC voltage (as of October 2026). A tachometer, an illuminance meter and a phase sequence indicator are not among these three.
Practice: answer the questions on this page
This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.
* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.
This page is a translation of the Japanese original. If the translation and the original differ, the Japanese version takes precedence. This translation was made with AI and may contain errors.Report a translation errorView the Japanese original