A lighting symbol is marked "CL". What is the fixture?
Pendant (ペンダント)
Ceiling-mounted luminaire (シーリング)
Chandelier (シャンデリヤ)
Recessed luminaire / downlight (埋込器具)
AnswerB. Ceiling-mounted luminaire (シーリング)
"CL" is a ceiling-mounted luminaire (fixed directly to the ceiling). A chandelier is "CH" and a recessed luminaire is "DL". A pendant (hung from a cord or chain) has its own symbol rather than a letter.
Q2 | Luminaire annotation CH
A lighting symbol is marked "CH". What is the fixture?
Chandelier (シャンデリヤ)
Ceiling-mounted luminaire (シーリング)
Recessed luminaire / downlight (埋込器具)
Fluorescent lamp (蛍光灯)
AnswerA. Chandelier (シャンデリヤ)
"CH" is a chandelier (a decorative multi-lamp fixture hung from the ceiling). The examination center's sample questions also ask for a chandelier. A ceiling-mounted luminaire is "CL" and a recessed luminaire is "DL". A fluorescent lamp has its own symbol rather than a letter.
Q3 | Luminaire annotation DL
A lighting symbol is marked "DL". What is the fixture?
Recessed luminaire / downlight (埋込器具)
Pendant (ペンダント)
Ceiling-mounted luminaire (シーリング)
Chandelier (シャンデリヤ)
AnswerA. Recessed luminaire / downlight (埋込器具)
"DL" is a recessed luminaire (downlight) set into the ceiling. A ceiling-mounted luminaire is "CL" and a chandelier is "CH". A pendant has its own symbol rather than a letter.
Q4 | Single-line diagram
In a wiring diagram (single-line diagram), what does one line between two devices represent?
Exactly one wire per line
Always exactly two wires
The wiring route, regardless of the number of wires
Always a three-core cable
AnswerC. The wiring route, regardless of the number of wires
A single-line diagram draws the two or three actual wires as one line, so the line shows the wiring route. One line is not necessarily one wire, and it is not fixed at two wires or three cores. The number of wires is worked out from the notes or a multi-line diagram.
Q5 | VVF1.6-2C
A wiring line is annotated "VVF1.6-2C". What does it mean?
VVF, 1.6 mm conductor diameter, 2 cores
VVF, 1.6 mm² conductor cross-section, 2 cores
VVF, 1.6 mm conductor diameter, 2 runs
VVF, 1.6 m long, 2 pieces
AnswerA. VVF, 1.6 mm conductor diameter, 2 cores
"1.6" is a solid conductor diameter of 1.6 mm and "2C" means two cores (two wires inside the cable). 1.6 is not a cross-sectional area (areas are used for stranded wires such as 5.5). "C" counts cores, not cable runs. Length is not annotated.
Q6 | IV5.5
A wiring line is annotated "IV5.5". What does "5.5" indicate?
Conductor diameter of 5.5 mm
The equivalent of 5.5 wires
Wire length of 5.5 m
Conductor cross-section of 5.5 mm²
AnswerD. Conductor cross-section of 5.5 mm²
Sizes such as 5.5, 8 and 14 are normally cross-sectional areas of stranded wire, so this is 5.5 mm². Solid wires such as 1.6 or 2.0 are given as diameters, but 5.5 is not a 5.5 mm solid wire. The number is not a count of wires or a length.
Q7 | VVR
Which cable does the annotation "VVR" denote?
600 V PVC-insulated PVC-sheathed cable, flat
600 V PVC-insulated wire
600 V cross-linked polyethylene-insulated PVC-sheathed cable
600 V PVC-insulated PVC-sheathed cable, round
AnswerD. 600 V PVC-insulated PVC-sheathed cable, round
The R in VVR stands for round: a 600 V PVC-insulated PVC-sheathed round cable. The flat type is VVF, 600 V PVC-insulated wire is IV, and the cross-linked polyethylene cable is CV.
Q8 | EM-EEF
Which cable does the annotation "EM-EEF" denote?
600 V PVC-insulated PVC-sheathed cable, flat
600 V polyethylene-insulated flame-retardant polyethylene-sheathed cable, flat
600 V cross-linked polyethylene-insulated PVC-sheathed cable
600 V PVC-insulated PVC-sheathed cable, round
AnswerB. 600 V polyethylene-insulated flame-retardant polyethylene-sheathed cable, flat
EM-EEF is a 600 V polyethylene-insulated, flame-retardant polyethylene-sheathed flat cable (EM = eco-material). The flat PVC cable is VVF, the round one is VVR, and the cross-linked polyethylene PVC-sheathed cable is CV.
Q9 | Conduit E19
A line is annotated "IV1.6×3(E19)". Which conduit does E19 indicate?
Threadless steel conduit (ねじなし電線管)
Flexible synthetic-resin conduit (合成樹脂製可とう電線管)
Rigid PVC conduit (硬質ポリ塩化ビニル電線管)
Type 2 flexible metal conduit (2種金属製可とう電線管)
AnswerA. Threadless steel conduit (ねじなし電線管)
"E" means threadless steel conduit, and 19 is its nominal size. Flexible synthetic-resin conduit is PF (or CD), rigid PVC conduit is VE, and Type 2 flexible metal conduit is F2.
Q10 | Conduit PF16
A line is annotated "(PF16)". Which conduit is it?
Threadless steel conduit (ねじなし電線管)
Type 2 flexible metal conduit (2種金属製可とう電線管)
Flexible synthetic-resin conduit (PF管)
Rigid PVC conduit (硬質ポリ塩化ビニル電線管)
AnswerC. Flexible synthetic-resin conduit (PF管)
PF is flexible synthetic-resin conduit (PF pipe). Threadless steel conduit is E, Type 2 flexible metal conduit is F2, and rigid PVC conduit is VE.
Q11 | Type 2 flexible metal conduit
Which annotation indicates Type 2 flexible metal conduit (2種金属製可とう電線管)?
(F2 17)
(E19)
(VE16)
(CD16)
AnswerA. (F2 17)
F2 is Type 2 flexible metal conduit. E19 is threadless steel conduit, VE16 is rigid PVC conduit, and CD16 is CD-type flexible synthetic-resin conduit.
Q12 | JIS for wiring symbols
Which JIS does the Electrical Engineers Examination Center name as the basis for the "graphical symbols for premises wiring" used in exam questions?
JIS C 0303:2000
JIS C 0617 series
JIS C 8303
JIS C 3342
AnswerA. JIS C 0303:2000
The examination center says exam symbols follow JIS in principle: JIS C 0303:2000 for premises wiring symbols and the JIS C 0617 series for general electrical graphical symbols. So JIS C 0617 is the standard for general electrical symbols, not premises wiring symbols. JIS C 8303 covers plugs and socket-outlets and JIS C 3342 covers 600 V PVC-sheathed cables; they are product standards, not symbol standards.
Q13 | Earth electrode annotation
An earth electrode symbol is annotated "ED". What does it mean?
Earth electrode for Class C earthing
Outlet with earthing pole
Earth electrode for Class D earthing
Outlet with earth terminal
AnswerC. Earth electrode for Class D earthing
Earth electrodes are annotated with the earthing class, EA to ED for Classes A to D, so ED is Class D. Class C is EC. An outlet with an earthing pole ("E") or earth terminal ("ET") is an annotation on the outlet symbol, not on an earth electrode.
Q14 | Luminaire annotation W
A lighting symbol is annotated "W". What does it show?
A floor-standing fixture
A rainproof fixture
An emergency fixture
A wall-mounted fixture
AnswerD. A wall-mounted fixture
"W" on a luminaire means wall-mounted. A floor-standing fixture is annotated "F". Rainproof is "WP"; "W" alone does not mean rainproof. Emergency lighting has its own symbol rather than an annotation.
Q15 | Switch annotation EX
A switch symbol (●) is annotated "EX". What does it mean?
Explosion-proof
Rainproof
Built-in confirmation lamp
Delay switch
AnswerA. Explosion-proof
"EX" means explosion-proof (for places where there is a risk of explosion). Rainproof is "WP", a built-in confirmation lamp is "L", and a delay switch is "D".
Q16 | Outlet annotation H
A wall outlet symbol is annotated "H". What does it mean?
With earthing pole
Locking type
Twist-lock (hook) type
Medical use
AnswerD. Medical use
"H" on an outlet means medical use. With earthing pole is "E", the locking type is "LK", and the twist-lock (hook) type is "T". The same "H" means a built-in locator lamp on a switch and an HID lamp ballast on a small transformer, so read it according to the symbol it is attached to.
Q17 | Pendant
In wiring diagrams, what kind of fixture is a "pendant" (ペンダント)?
A fixture mounted directly on the ceiling
A fixture hung from the ceiling by a cord or chain
A fixture recessed into the ceiling
A fixture mounted on the wall
AnswerB. A fixture hung from the ceiling by a cord or chain
A pendant hangs from the ceiling by a cord, chain or similar. A fixture mounted directly on the ceiling is a ceiling luminaire (CL), one recessed into the ceiling is a recessed luminaire (DL), and one on the wall is wall-mounted (W).
Q18 | Luminaire capacity annotation
A lighting symbol is annotated "40W×2". What does it mean?
Two circuits of fixtures rated 40 A
Two 40 W fixtures shown by one symbol
A 40 W fixture with two lighting levels
A fixture that uses two 40 W lamps
AnswerD. A fixture that uses two 40 W lamps
Luminaire capacity is annotated as "watts × number of lamps", so "40W×2" is a fixture using two 40 W lamps. W is a unit of power, not current (A). The annotation does not count fixtures or lighting levels.
Q19 | Switch annotation 2P
A switch symbol (●) is annotated "2P". What does it mean?
Two switches mounted side by side (2-gang)
A switch rated 2 A
A two-pole switch
A switch operated from two places
AnswerC. A two-pole switch
"P" gives the number of poles, so "2P" is a two-pole switch. A switch that controls one light from two places is a three-way switch, annotated "3". Current is written with A, so "2P" is not 2 A, and "2P" does not count gangs.
Q20 | Switch annotation 3
What is the name of the switch in the figure?
Three-pole switch
Triple-gang switch
Three-way switch (3路スイッチ)
Switch rated 3 A
AnswerC. Three-way switch (3路スイッチ)
The annotation "3" on a switch means a three-way switch (controls one light from two places). Poles would be written with P, as in "2P". A bare "3" is not used for three gangs or for a 3 A rating.
Q21 | Switch annotation 4
What is the switch in the figure used for?
Combined with three-way switches to control a light from three or more places
Controlling four lights separately from one place
Switching off automatically after four seconds
Switching only lights rated 4 A
AnswerA. Combined with three-way switches to control a light from three or more places
The annotation "4" means a four-way switch, placed between two three-way switches so one light can be controlled from three or more places. It does not operate four lights separately, and it does not indicate time or current.
Q22 | Switch annotation H
What does the annotation "H" on the switch in the figure mean?
Built-in confirmation lamp (lit when ON)
Built-in locator lamp (lit when OFF)
Passive-infrared automatic switch
Switch only for HID lamps
AnswerB. Built-in locator lamp (lit when OFF)
The annotation "H" on a switch means a built-in locator lamp, which glows when the switch is OFF so it can be found in the dark. A confirmation lamp that glows when ON is "L", and a passive-infrared automatic switch is "RAS". It does not mean a switch only for HID lamps.
Q23 | Switch annotation L
You want to check from another place that a ventilation fan is running. Which annotation on the switch symbol is appropriate?
H
T
L
P
AnswerC. L
A confirmation lamp glows when the switch is ON to show the load is operating; the built-in type is annotated "L". "H" is a built-in locator lamp that glows when OFF, "T" is with timer, and "P" is a pull switch.
Q24 | Automatic light switch
What is the name of the switch in the figure (annotated A(3A))?
The annotation "A" with the capacity (3A) is an automatic light switch used for outdoor lights, switching by ambient brightness. A passive-infrared automatic switch is "RAS", a delay switch is "D", and a remote-control switch is "R".
Q25 | Delay switch
Which describes the switch in the figure (annotated D)?
It turns on automatically when it gets dark
It turns off a set time after being switched off
It switches on and off by sensing body heat (infrared)
It is operated by pulling a cord
AnswerB. It turns off a set time after being switched off
The annotation "D" is a delay switch: it actually turns off a set time after it is switched off (used for fans, for example). Turning on in the dark is the automatic light switch "A", sensing body heat is the passive-infrared switch "RAS", and a cord-operated switch is the pull switch "P".
Q26 | Passive-infrared switch
You want the entrance light to turn on automatically when a person approaches. Which switch symbol is used in the wiring diagram?
●A(3A)
●RAS
●D
●T
AnswerB. ●RAS
A switch that senses infrared heat from the human body is the passive-infrared automatic switch, annotated "RAS". "A(3A)" is an automatic light switch that reacts to brightness, "D" is a delay switch, and "T" has a timer; none of them detects people.
Q27 | Switch with no annotation
What does a switch symbol with no annotation (a plain black dot) represent?
A three-way switch rated 15 A
A single-pole switch rated 20 A
A single-pole switch rated 15 A
A two-pole switch rated 15 A
AnswerC. A single-pole switch rated 15 A
For switches, a 15 A rating and single-pole type are not annotated, so a plain black dot is a single-pole 15 A switch. A three-way switch has "3", a two-pole switch has "2P", and ratings other than 15 A are written next to the symbol.
Q28 | Outlet annotation E
A wall outlet symbol is annotated "E". What does it mean?
With earth terminal
With built-in earth leakage breaker
Explosion-proof
With earthing pole
AnswerD. With earthing pole
The annotation "E" on an outlet means it has an earthing pole (an earth contact in the socket). With earth terminal is "ET", with earth leakage breaker is "EL", and explosion-proof is "EX".
Q29 | Outlet annotation EL
A wall outlet symbol is annotated "EL". What does it mean?
With built-in earth leakage breaker
With earthing pole and earth terminal
Locking (pull-out prevention) type
Medical use
AnswerA. With built-in earth leakage breaker
"EL" is an outlet with a built-in earth leakage breaker. With earthing pole and earth terminal is "EET", the locking type is "LK", and medical use is "H".
Q30 | Outlet annotation LK
Which annotation indicates a locking outlet (抜け止め形), where the plug is turned so it does not come out easily?
T
LK
ET
WP
AnswerB. LK
The locking (pull-out prevention) type is annotated "LK". "T" is the twist-lock hook type that uses a special plug, "ET" is with earth terminal, and "WP" is rainproof.
Q31 | Outlet items not annotated
For a wall outlet symbol, which item is NOT annotated?
A rating of 20 A
A rating of 250 V
A rating of 15 A, 125 V
Three poles
AnswerC. A rating of 15 A, 125 V
A general outlet rated 15 A, 125 V is not annotated. Ratings of 20 A or more (current), 250 V or more (voltage), and three or more poles are annotated.
Q32 | Letters for breakers and switches
In a wiring diagram, which set of letters is used in the symbols for a molded-case circuit breaker, an earth leakage breaker and a switch (disconnector), in that order?
E, B, S
B, E, S
S, E, B
B, S, E
AnswerB. B, E, S
A molded-case circuit breaker is "B", an earth leakage breaker is "E", and a switch (disconnector) is "S". The other sets mix up the letters. Do not confuse the "E" of an earth leakage breaker with the outlet annotation "E" (with earthing pole).
Q33 | Outlet annotation 2
A wall outlet symbol is annotated "2". What does it mean?
Two poles
Rated 20 A
Dedicated to two appliances
Duplex (two sockets)
AnswerD. Duplex (two sockets)
A bare number on an outlet gives the number of sockets, so "2" is a duplex outlet. Poles are written with P, such as "3P", and only for three or more poles. Current is written with A, as in "20A". It does not count appliances.
Q34 | Rated sensitivity current
An earth leakage breaker symbol is annotated "2P 20A 30mA". What does 30mA represent?
Rated current
Rated sensitivity current
Frame size
Fuse rated current
AnswerB. Rated sensitivity current
The mA value on an earth leakage breaker is the rated sensitivity current, the leakage current at which it operates. 20A is the rated current. Frame size is not given in mA, and a fuse rating is annotated on a switch (disconnector).
Q35 | Circuit breaker annotations
Which item is NOT annotated on a molded-case circuit breaker symbol?
Number of poles
Frame size
Rated current
Rated sensitivity current
AnswerD. Rated sensitivity current
A molded-case circuit breaker is annotated with poles, frame size and rated current. Rated sensitivity current is a value for leakage detection, so it belongs on earth leakage breakers, not on molded-case circuit breakers.
Q36 | Watt-hour meter letters
In a wiring diagram, which instrument has the letters "Wh" in its symbol?
Wattmeter (電力計)
Watt-hour meter (電力量計)
Ammeter (電流計)
Voltmeter (電圧計)
AnswerB. Watt-hour meter (電力量計)
"Wh" (watt-hour) is a unit of energy, so it is the watt-hour meter, which measures the energy used. A wattmeter measures instantaneous power (W), an ammeter measures current (A), and a voltmeter measures voltage (V).
Q37 | Motor annotation
A motor symbol is annotated "3φ200V 0.75kW". What does it mean?
Single-phase three-wire 200 V, 0.75 kW
Three-phase 200 V, rated current 0.75 A
Three 200 V motors totalling 0.75 kW
Three-phase 200 V, 0.75 kW capacity
AnswerD. Three-phase 200 V, 0.75 kW capacity
Motors are annotated with the electrical system, voltage and capacity. "3φ" means three-phase, "200V" is the voltage and "0.75kW" is the capacity. "3φ" means three-phase, so it is not single-phase three-wire. kW is a unit of power, not current (A), and the annotation does not count motors.
Q38 | Small transformer H
A small transformer symbol is annotated "H". What does it mean?
Medical use
Built-in locator lamp
Ballast for HID lamps
Bell transformer
AnswerC. Ballast for HID lamps
"H" on a small transformer means a ballast for HID lamps. Medical use is the "H" on an outlet and a built-in locator lamp is the "H" on a switch; they are not small-transformer annotations. A bell transformer is "B".
Q39 | Small transformer B
A small transformer symbol (letter T) is annotated "B". What is the device?
Remote-control transformer (リモコン変圧器)
Neon transformer (ネオン変圧器)
Fluorescent lamp ballast (蛍光灯用安定器)
Bell transformer (ベル変圧器)
AnswerD. Bell transformer (ベル変圧器)
"T" is a small transformer, and the annotation "B" means a bell transformer (for chimes and bells). A remote-control transformer is "R", a neon transformer is "N", and a fluorescent lamp ballast is "F".
Q40 | Room air conditioner O
A room air conditioner symbol (letters RC) is annotated "O". What does it mean?
Outdoor unit
Indoor unit
Ceiling-mounted
Rainproof
AnswerA. Outdoor unit
For room air conditioners, the outdoor unit is annotated "O" and the indoor unit "I". "O" does not mean ceiling-mounted or rainproof (rainproof is WP).
Practice: answer the questions on this page
This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.
* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.