Read the questions and explanations in English. The lectures (explanatory articles) are available in Japanese only.

View the Japanese version (with lectures) →

Q1 | Name of VVF

Which is the correct name of the wire marked "VVF"?

  1. 600 V PVC insulated wire
  2. 600 V PVC insulated PVC sheathed cable, round type
  3. 600 V PVC insulated PVC sheathed cable, flat type
  4. PVC insulated drop wire
AnswerC. 600 V PVC insulated PVC sheathed cable, flat type

The correct answer is "600 V PVC insulated PVC sheathed cable, flat type". V stands for vinyl (PVC) and F for flat, so VVF is a flat cable with PVC insulation and a PVC sheath. "600 V PVC insulated wire" is IV (insulated wire with no sheath), the round-type cable is VVR, and "PVC insulated drop wire" is the name of DV.

Q2 | Reading a wire label

A wiring diagram says "VVF 2.0-3C". Which correctly explains this label?

  1. Solid conductors 2.0 mm in diameter, with 3 cores
  2. Stranded conductors of 2.0 mm² area, with 3 cores
  3. Solid conductors 2.0 mm in diameter, 3 m long
  4. Solid conductors 3.0 mm in diameter, with 2 cores
AnswerA. Solid conductors 2.0 mm in diameter, with 3 cores

The correct answer is "Solid conductors 2.0 mm in diameter, with 3 cores". The size of a solid wire is shown by its diameter (mm), and "3C" means three cores. The option reading "2.0" as a cross-sectional area of stranded wire is wrong (area in mm², such as 5.5, is used for stranded wire). The option saying "3 m long" is wrong because "C" does not mean length. The option with 3.0 mm and 2 cores mixes up the order of the numbers.

Q3 | Insulated wire vs. cable

Which correctly describes the difference between an insulated wire and a cable?

  1. Insulated wire has stranded conductors; cable has solid conductors
  2. Insulated wire is for outdoors only; cable is for indoors only
  3. Insulated wire uses copper; cable uses aluminium
  4. A cable has a sheath that covers the outside of the insulation
AnswerD. A cable has a sheath that covers the outside of the insulation

The correct answer is "A cable has a sheath that covers the outside of the insulation". A conductor wrapped in insulation is an insulated wire; when a sheath (outer jacket) is added over that, it is a cable. The option about stranded vs. solid conductors is wrong: both come in solid and stranded types. The option about outdoors only vs. indoors only is wrong: insulated wires such as IV are used indoors, and cables can be used outdoors. The option about copper vs. aluminium is wrong: the conductor material is not what separates them.

Q4 | Wire for a service drop

Which insulated wire is used for a low-voltage overhead service drop from a utility pole to a house?

  1. IV
  2. DV
  3. VVR
  4. HIV
AnswerB. DV

The correct answer is "DV". DV is "PVC insulated drop wire" (引込用ビニル絶縁電線), made for overhead service drops. IV and HIV are insulated wires used indoors, for example inside conduit. VVR is a round cable, not an insulated wire.

Q5 | Wire not allowed in conduit

Under the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), which wire may NOT be used for metal conduit or plastic conduit work?

  1. 600 V PVC insulated wire (solid, 1.6 mm)
  2. 600 V grade 2 PVC insulated wire (HIV)
  3. PVC insulated wire for outdoor use (OW)
  4. 600 V PVC insulated wire (stranded, 5.5 mm²)
AnswerC. PVC insulated wire for outdoor use (OW)

The correct answer is "PVC insulated wire for outdoor use (OW)". Articles 158 and 159 of the Interpretation require "insulated wire (excluding PVC insulated wire for outdoor use)", so OW cannot be used. The 1.6 mm solid IV and the grade 2 PVC insulated wire (HIV) are insulated wires and solid wires of 3.2 mm or less, so they are allowed. The 5.5 mm² wire is stranded, so it is allowed.

Q6 | Features of EM-EEF

Which correctly describes EM-EEF (600 V flame-retardant polyethylene insulated, flame-retardant polyethylene sheathed flat cable)?

  1. It gives off little halogen gas when burned
  2. Both its insulation and sheath are PVC
  3. An insulated wire only for outdoor overhead lines
  4. A soft wire only for moving equipment
AnswerA. It gives off little halogen gas when burned

The correct answer is "It gives off little halogen gas when burned". EM stands for eco-material. Its insulation and sheath are flame-retardant polyethylene, so it gives off little halogen-containing gas when it burns. The option saying both insulation and sheath are PVC describes VVF. The option about outdoor overhead lines describes OW; EM-EEF is a sheathed cable. The option about a soft wire for moving equipment describes cabtyre cable.

Q7 | Identify by cross-section
sheath insulation conductor

The figure is a sketch of the cross-section of a wire. Three insulated conductors lie side by side inside one flat outer sheath. Which symbol best matches this wire?

  1. IV
  2. VVF
  3. VVR
  4. DV
AnswerB. VVF

The correct answer is "VVF". It has a sheath, so it is a cable, and its cross-section is flat, so it is VVF. IV is just one conductor with insulation and no sheath. VVR is a cable with a round cross-section. DV is an insulated drop wire, not three wires lying in one flat sheath.

Q8 | Thickness of metal conduit

Under the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), what is the minimum thickness of metal conduit embedded in concrete for low-voltage indoor wiring?

  1. 0.5 mm
  2. 0.8 mm
  3. 1.0 mm
  4. 1.2 mm
AnswerD. 1.2 mm

The correct answer is "1.2 mm". Article 159(2)(ii) requires metal conduit embedded in concrete to be at least 1.2 mm thick. 0.5 mm is for conduit 4 m or shorter without joints in dry, exposed places. 1.0 mm is for other places. 0.8 mm is one of the conditions for using Type 1 flexible metal conduit, not a value for metal conduit.

Q9 | Name of CV

Which is the correct name of the cable marked "CV"?

  1. 600 V polyethylene insulated, flame-retardant polyethylene sheathed cable
  2. 600 V PVC insulated PVC sheathed cable, round type
  3. 600 V cross-linked polyethylene insulated PVC sheathed cable
  4. PVC cabtyre cable
AnswerC. 600 V cross-linked polyethylene insulated PVC sheathed cable

The correct answer is "600 V cross-linked polyethylene insulated PVC sheathed cable". C stands for cross-linked polyethylene insulation and V for a PVC sheath. Cables insulated with cross-linked polyethylene are covered by JIS C 3605 (600 V polyethylene insulated cables). The polyethylene insulated, flame-retardant polyethylene sheathed cable is wrong because its insulation is not cross-linked polyethylene and its sheath is not PVC. The round-type PVC sheathed cable is VVR, and PVC cabtyre cable is VCT.

Q10 | Wiring for moving equipment

In a factory, which wire is most suitable for supplying a machine that is moved from place to place while in use?

  1. 600 V PVC insulated wire (IV)
  2. PVC insulated wire for outdoor use (OW)
  3. PVC insulated drop wire (DV)
  4. PVC cabtyre cable (VCT)
AnswerD. PVC cabtyre cable (VCT)

The correct answer is "PVC cabtyre cable (VCT)". Cabtyre cable uses soft stranded conductors covered by a tough sheath, so it suits equipment that is moved during use (Article 8 of the Interpretation covers cabtyre cables). IV, OW and DV are insulated wires without a sheath and are not suited to wiring that moves.

Q11 | Threadless conduit to a box

Which fitting is used to connect threadless steel conduit to an outlet box?

  1. TS coupling
  2. Threadless box connector
  3. Threadless coupling
  4. Normal bend
AnswerB. Threadless box connector

The correct answer is "Threadless box connector". A threadless box connector joins the conduit to the box, and a locknut tightens it from inside the box. A TS coupling joins rigid PVC conduits together. A threadless coupling joins two threadless conduits. A normal bend is a curved piece of conduit for right-angle joints.

Q12 | Tightening the set screw

How should the set screw of a threadless box connector be tightened?

  1. Tighten it until the head twists off
  2. Tighten lightly by hand so it can be removed later
  3. Do not tighten it; fix with the locknut only
  4. Do not use it; glue the conduit in place instead
AnswerA. Tighten it until the head twists off

The correct answer is "Tighten it until the head twists off". The exam centre's defect criteria list "set screw not twisted off" on a threadless bushing or threadless box connector as a defect. Tightening lightly by hand, or relying on the locknut only, does not hold the conduit firmly. As for the option using glue: glue is used for rigid PVC conduit (TS couplings), not for metal conduit.

Q13 | Insulating bushing

What is the role of an insulating bushing in metal conduit work?

  1. To join two conduits in a straight line
  2. To fix the conduit to a wall or other structure
  3. To pass a pull line into the conduit
  4. To protect wire insulation at the conduit opening
AnswerD. To protect wire insulation at the conduit opening

The correct answer is "To protect wire insulation at the conduit opening". An insulating bushing is fitted on the open end of a conduit so that the wire insulation is not damaged on the edge when wires are pulled in or out. Joining conduits in a straight line is the job of a coupling, fixing conduit to a structure is a saddle, and passing a pull line is a fish tape (呼び線挿入器).

Q14 | Fitting on a vertical pipe top
outer wall fitting on the pipe top wires metal conduit (vertical)

As shown, which fitting is attached to the top of an outdoor metal conduit that rises vertically, with its opening facing down to keep rain out?

  1. Terminal cap
  2. Universal fitting
  3. Entrance cap
  4. Normal bend
AnswerC. Entrance cap

The correct answer is "Entrance cap". An entrance cap is used on the end of a vertical conduit; its opening faces down, so rain does not easily get in. The terminal cap is used on horizontal conduit ends; on a vertical pipe water could enter. A universal fitting is used where exposed conduit turns a right angle, and a normal bend is a curved length of conduit.

Q15 | Right-angle point in exposed conduit

Which fitting is used where exposed metal conduit turns at a right angle?

  1. Coupling
  2. Universal fitting
  3. Saddle
  4. Locknut
AnswerB. Universal fitting

The correct answer is "Universal fitting". A universal fitting is used where exposed conduit turns a right angle. A coupling joins conduits in a straight line, a saddle fixes the conduit to a structure, and a locknut is a nut that clamps a connector to the wall of a box.

Q16 | PF and CD conduit

Which statement about PF and CD pliable plastic conduit is correct?

  1. CD conduit is not self-extinguishing and is embedded in concrete
  2. CD conduit is only for exposed indoor runs and cannot go in concrete
  3. PF conduit must not be embedded in concrete
  4. Both PF and CD conduit are rigid and must be heated to bend
AnswerA. CD conduit is not self-extinguishing and is embedded in concrete

The correct answer is "CD conduit is not self-extinguishing and is embedded in concrete". CD conduit is not self-extinguishing; under Article 158 of the Interpretation it must be embedded directly in concrete or placed in a dedicated non-combustible or self-extinguishing flame-retardant pipe or duct. The option saying CD conduit is only for exposed indoor runs is the reverse: CD conduit cannot be used on its own for exposed runs. The option saying PF conduit must not be embedded in concrete is wrong: PF conduit can be embedded in concrete and also used for exposed or concealed indoor runs. The option saying both are rigid and must be heated describes rigid PVC conduit; pliable conduit can be bent by hand.

Q17 | Joining rigid PVC conduit

Which fitting joins two rigid PVC conduits using adhesive?

  1. Threadless coupling
  2. Combination coupling
  3. Straight box connector
  4. TS coupling
AnswerD. TS coupling

The correct answer is "TS coupling". A TS coupling joins rigid PVC conduits with adhesive. A threadless coupling joins threadless steel conduits with set screws, a combination coupling joins different types of conduit (such as flexible metal conduit and steel conduit), and a straight box connector connects flexible metal conduit to a box.

Q18 | Flexible conduit to steel conduit

Which fitting joins flexible metal conduit to steel conduit?

  1. Combination coupling
  2. TS coupling
  3. Entrance cap
  4. Rubber grommet
AnswerA. Combination coupling

The correct answer is "Combination coupling". A combination coupling joins two different kinds of conduit, such as flexible metal conduit and steel conduit. A TS coupling joins rigid PVC conduits, an entrance cap goes on the top of a vertical conduit, and a rubber grommet is used where a cable passes through a hole in a box.

Q19 | Protecting a cable at a box hole

When VVF cable passes through a hole in a metal box, which item is fitted so the cable is not damaged by the edge of the hole?

  1. Locknut
  2. Saddle
  3. Rubber grommet
  4. Normal bend
AnswerC. Rubber grommet

The correct answer is "Rubber grommet". A rubber grommet (ゴムブッシング) is fitted into the hole to cover its edge so the cable sheath is not damaged. The defect criteria also list improper use of a rubber grommet. A locknut fixes connectors or conduit, a saddle fixes conduit or cable, and a normal bend is for right-angle conduit runs.

Q20 | Joints inside conduit

In metal conduit work, which statement about where wires may be joined is correct?

  1. Joints inside the conduit are allowed if well taped
  2. No joints inside the conduit; join wires inside a box
  3. Joints inside the conduit are allowed if it is short
  4. Joints inside the conduit are allowed with push-in connectors
AnswerB. No joints inside the conduit; join wires inside a box

The correct answer is "No joints inside the conduit; join wires inside a box". Article 159 of the Interpretation says there must be no joints in the wires inside metal conduit (the same applies to plastic and flexible metal conduit). Joints are made inside an outlet box or similar. The other options (taping well, a short conduit, push-in connectors) all join wires inside the conduit, so they are wrong.

Q21 | Removing burrs inside conduit

After cutting a metal conduit, which tool removes the burrs inside the pipe?

  1. Hole saw
  2. Pipe bender
  3. Fish tape
  4. Reamer
AnswerD. Reamer

The correct answer is "Reamer". A reamer has a cone-shaped blade; it is turned with a brace (クリックボール) to remove burrs from the inside of the pipe. A hole saw cuts round holes in metal sheet, a pipe bender bends metal conduit, and a fish tape pulls a line through conduit.

Q22 | Insertion depth of plastic conduit

Two rigid PVC conduits are joined with a TS coupling and adhesive. Under Article 158 of the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), at least how many times the conduit outer diameter must the insertion depth be?

  1. 0.8 times
  2. 1.2 times
  3. 0.5 times
  4. 1.5 times
AnswerA. 0.8 times

The correct answer is "0.8 times". Article 158(3)(ii) sets the insertion depth between conduits, and between conduit and box, at 1.2 times the outer diameter or more, or 0.8 times or more when adhesive is used. 1.2 times is the value without adhesive. 0.5 times and 1.5 times do not appear in the Interpretation.

Q23 | Bending rigid PVC conduit

When bending rigid PVC conduit, which tool is used to heat the pipe?

  1. Pipe bender
  2. Chamfering tool
  3. Gas torch
  4. Pipe cutter
AnswerC. Gas torch

The correct answer is "Gas torch". Rigid PVC conduit is warmed with a gas torch to soften it before bending. A pipe bender bends metal conduit and cannot heat plastic pipe. A chamfering tool removes the sharp edge of a cut plastic pipe, and a pipe cutter cuts pipe.

Q24 | Large hole in sheet steel

Which tool punches a large round hole in a metal box or the steel plate of a distribution board to pass conduit through?

  1. Auger bit
  2. Knockout punch
  3. Plastic pipe cutter
  4. Wire stripper
AnswerB. Knockout punch

The correct answer is "Knockout punch". A knockout punch punches large round holes in metal plate. An auger bit is for drilling holes in wood, not steel. A plastic pipe cutter cuts plastic conduit, and a wire stripper strips insulation from wires.

Q25 | Hole in wood

In a wooden house, which tool drills a hole in a wooden post or board to pass wires through?

  1. Reamer
  2. Knockout punch
  3. Auger bit
  4. Pipe cutter
AnswerC. Auger bit

The correct answer is "Auger bit". An auger bit (羽根ぎり) drills holes in wood and is used with a brace or a drill. A reamer removes burrs inside metal conduit, a knockout punch punches holes in metal plate, and a pipe cutter cuts pipe.

Q26 | Hole in concrete

Which tool drills holes in a concrete wall for mounting equipment?

  1. Hammer drill
  2. Auger bit
  3. Chamfering tool
  4. Wire stretcher
AnswerA. Hammer drill

The correct answer is "Hammer drill". A hammer drill (振動ドリル) adds a hammering action to rotation to drill concrete. An auger bit is for wood. A chamfering tool removes the edge of cut plastic conduit and a wire stretcher tightens overhead wire; neither drills holes.

Q27 | Passing a line through conduit

Which tool feeds a pull line through a conduit before the wires are drawn in?

  1. Bolt clipper
  2. Water pump pliers
  3. Brace
  4. Fish tape
AnswerD. Fish tape

The correct answer is "Fish tape". A fish tape (呼び線挿入器) pushes a coiled line through the conduit; the wires are then tied to it and pulled in. A bolt clipper cuts thick wire or bolts, water pump pliers are used for tightening locknuts, and a brace is a hand tool that turns reamers or auger bits.

Q28 | Crimping a ring sleeve

When joining wires with a ring sleeve (リングスリーブ), which tool is used to crimp the sleeve?

  1. Pliers
  2. Crimping tool for ring sleeves
  3. Crimping tool for bare terminals
  4. Water pump pliers
AnswerB. Crimping tool for ring sleeves

The correct answer is "Crimping tool for ring sleeves". Ring sleeves are crimped with the crimping tool made for ring sleeves. The crimping tool for bare terminals looks similar but is for bare crimp terminals, not ring sleeves. Squeezing with pliers or water pump pliers does not give the required crimp. The defect criteria also treat improper use of the crimping tool as a defect.

Q29 | Tightening a locknut

Which adjustable-jaw tool is used to tighten a locknut inside a box?

  1. Wire stripper
  2. Pipe cutter
  3. Water pump pliers
  4. Electrician's knife
AnswerC. Water pump pliers

The correct answer is "Water pump pliers". Water pump pliers have jaws that adjust in steps, so they can grip and tighten a locknut. A wire stripper strips insulation, a pipe cutter cuts pipe, and an electrician's knife is a blade for removing sheath or insulation; none of them can tighten a nut.

Q30 | Stripping insulation

Which tool is made for stripping wire insulation, using blades sized for each wire thickness?

  1. Bolt clipper
  2. Reamer
  3. Pipe bender
  4. Wire stripper
AnswerD. Wire stripper

The correct answer is "Wire stripper". A wire stripper has blade holes for each wire size and strips the insulation. A bolt clipper cuts thick wire or bolts and cannot remove only the insulation. A reamer removes burrs inside conduit, and a pipe bender bends metal conduit.

Practice: answer the questions on this page

This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.

* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.