Q1 | Synchronous speed

What is the synchronous speed [min⁻¹] of a 4-pole three-phase induction motor (三相誘導電動機) at 50 Hz?

  1. 1200
  2. 1500
  3. 1800
  4. 3000
AnswerB. 1500

Ns = 120f / p = 120 × 50 / 4 = 1500 min⁻¹. 1800 is the value for 4 poles at 60 Hz, 3000 for 2 poles at 50 Hz, and 1200 for 6 poles at 60 Hz.

Q2 | Operating time of circuit breakers

Under Article 33 of the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), which performance is required of a circuit breaker (配線用遮断器) rated 30 A or less in a low-voltage circuit (excluding those covered by the Electrical Appliances and Materials Safety Act and some others)?

  1. Trips automatically within 60 minutes at 1 times its rated current
  2. Trips automatically within 2 minutes at 1.25 times its rated current
  3. Need only trip automatically within 60 minutes at 2 times its rated current
  4. Trips automatically within 60 minutes at 1.25 times and within 2 minutes at 2 times its rated current
AnswerD. Trips automatically within 60 minutes at 1.25 times and within 2 minutes at 2 times its rated current

Article 33(3) and Table 33-2 require a circuit breaker rated 30 A or less to trip within 60 minutes at 1.25 times and within 2 minutes at 2 times its rated current. The option "within 60 minutes at 1 times" is wrong: it must NOT trip automatically at 1 times its rated current. The option "within 2 minutes at 1.25 times" mixes up the times for 1.25 times (60 minutes) and 2 times (2 minutes). The option "within 60 minutes at 2 times" is too slow: at 2 times it must trip within 2 minutes.

Q3 | Calculating slip

A three-phase induction motor with a synchronous speed of 1800 min⁻¹ runs at 1746 min⁻¹. What is the slip (すべり)?

  1. 3%
  2. 5%
  3. 54%
  4. 97%
AnswerA. 3%

s = (Ns − N) / Ns = (1800 − 1746) / 1800 = 54 / 1800 = 0.03 = 3%. 54 is the speed difference, not a ratio. 97% is N / Ns, the opposite of slip. 5% is a calculation error.

Q4 | Rotational speed

A 4-pole three-phase induction motor runs at 60 Hz with a slip of 4%. What is its rotational speed [min⁻¹]?

  1. 1440
  2. 1728
  3. 1800
  4. 1872
AnswerB. 1728

Ns = 120 × 60 / 4 = 1800. N = 1800 × (1 − 0.04) = 1728 min⁻¹. 1800 is the synchronous speed itself, 1872 wrongly adds the slip, and 1440 applies the slip to the 50 Hz synchronous speed of 1500.

Q5 | Frequency and speed

The same three-phase induction motor is moved from a 50 Hz area to a 60 Hz area and used at the same voltage. Roughly how does its speed change?

  1. About 0.83 times
  2. No change
  3. About 1.44 times
  4. About 1.2 times
AnswerD. About 1.2 times

Synchronous speed is proportional to frequency: 60 / 50 = 1.2. With similar slip, the speed also becomes about 1.2 times. 0.83 is the reverse direction, 1.44 wrongly squares 1.2, and speed does change with frequency even if the number of poles is the same.

Q6 | Reversing rotation

Which is a correct way to reverse the rotation of a three-phase induction motor?

  1. Swap two of the three supply wires
  2. Shift all three supply wires by one position
  3. Lower the supply voltage slightly
  4. Connect a power-factor capacitor in parallel
AnswerA. Swap two of the three supply wires

Swapping two wires reverses the phase sequence, so the rotating magnetic field turns the other way. Shifting all three keeps the same phase sequence. Lowering the voltage changes speed or torque, not direction. A power-factor capacitor (進相コンデンサ) improves power factor and has nothing to do with direction.

Q7 | Star-delta starting current

With star-delta (Y−Δ) starting (スターデルタ始動), the starting line current of a three-phase induction motor is about how many times that of direct full-voltage starting?

  1. 1/√3
  2. 1/3
  3. √3
  4. 3
AnswerB. 1/3

In star, each winding voltage is 1/√3, so the winding current is 1/√3. In delta, the line current is √3 times the winding current, but in star they are equal. So (1/√3) ÷ √3 = 1/3. 1/√3 looks only at one winding; √3 and 3 go in the wrong direction.

Q8 | Purpose of star-delta starting

Which statement about star-delta starting is correct?

  1. It is a way to increase starting torque
  2. The motor keeps running in star after starting
  3. It reduces starting current, but starting torque also drops
  4. It is a method for starting single-phase induction motors
AnswerC. It reduces starting current, but starting torque also drops

In star the voltage is lower, so starting current drops to 1/3; torque is proportional to voltage squared, so starting torque also drops to 1/3. It does not increase torque. After speeding up, the motor is switched to delta. It switches windings between star and delta, so it is used for three-phase motors.

Q9 | Power factor correction

How is a power-factor capacitor (進相コンデンサ) used to improve the power factor of a three-phase induction motor?

  1. Connected in series with the motor
  2. Connected in parallel with the motor
  3. Connected between the motor frame and the earth
  4. Connected in place of the thermal relay of the magnetic switch
AnswerB. Connected in parallel with the motor

The capacitor is connected in parallel with the motor. It cancels the lagging current, raises the power factor and reduces the current in the wires. It is not in series. The frame-to-earth connection is the grounding wire's job. A thermal relay provides overload protection, which a capacitor cannot replace.

Q10 | Motor overload protection

Under Article 65 of the Ministerial Ordinance on Technical Standards for Electrical Equipment (電気設備に関する技術基準を定める省令), which indoor motors are excluded from the requirement to prevent fire from burnout by overcurrent?

  1. Motors with output of 0.2 kW or less
  2. Motors with output of 2 kW or less
  3. Three-phase 200 V motors
  4. Single-phase 100 V motors
AnswerA. Motors with output of 0.2 kW or less

Article 65 excludes motors with an output of 0.2 kW or less, not 2 kW. There is no exclusion based on voltage (three-phase 200 V or single-phase 100 V).

Q11 | Magnetic switch

A magnetic switch (電磁開閉器) used to start, stop and protect a motor against overload is a combination of which devices?

  1. A circuit breaker and an earth leakage breaker
  2. A magnetic contactor and a power-factor capacitor
  3. A magnetic contactor and a thermal overload relay
  4. A timer switch and an automatic light switch
AnswerC. A magnetic contactor and a thermal overload relay

A magnetic switch combines a magnetic contactor (電磁接触器), which opens and closes contacts with an electromagnet, and a thermal overload relay (熱動継電器), which detects overload current by heat. The breakers belong in the distribution board, the capacitor improves power factor, and the timer and automatic switch control lighting.

Q12 | Unit of illuminance

What does the lux [lx], the unit of illuminance (照度), mean?

  1. The light energy a source emits per second
  2. The illuminance when 1 m² is lit by 1 lm of luminous flux
  3. The strength of light a source emits in one direction
  4. The luminous flux emitted per 1 W of power
AnswerB. The illuminance when 1 m² is lit by 1 lm of luminous flux

The Measurement Units Order (計量単位令) defines lux as the illuminance when a 1 m² surface is lit by 1 lm of luminous flux. Light strength in a direction is luminous intensity (cd), flux per watt is luminous efficacy (lm/W), and energy is in watts or joules, not lux.

Q13 | When an ELCB may be omitted

Under Article 36 of the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), in which case may an earth-fault interrupting device (such as an earth leakage circuit breaker, 漏電遮断器) be omitted from a circuit supplying low-voltage equipment over 60 V with a metal enclosure?

  1. Equipment at 100 V to earth installed in a place exposed to water
  2. Equipment at 200 V to earth installed in a damp place
  3. Equipment with Class D earthing (D種接地工事) of 100 Ω
  4. Equipment installed in a dry place
AnswerD. Equipment installed in a dry place

Article 36(1)(ii)(b) makes an exception for equipment installed in a dry place. The option "100 V to earth in a place exposed to water" is wrong: the exception for 150 V or less to earth applies only to places other than those exposed to water. The option "200 V to earth in a damp place" is not a dry place, and the voltage to earth is over 150 V. The option "Class D earthing of 100 Ω" is wrong: the earthing exception requires a Class C or D earthing resistance of 3 Ω or less.

Q14 | Calculating illuminance

A small light source with a luminous intensity of 360 cd points straight down. What is the illuminance [lx] on the floor 3 m directly below?

  1. 40
  2. 120
  3. 1080
  4. 3240
AnswerA. 40

E = I / r² = 360 / 3² = 360 / 9 = 40 lx. 120 divides without squaring the distance, 1080 multiplies by the distance, and 3240 multiplies by the distance squared.

Q15 | When motor overload protection may be omitted

Under Article 153 of the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), in which case may the overload protection device of an indoor motor be omitted?

  1. A three-phase motor whose supply-side circuit breaker is rated 20 A or less
  2. A motor with an output of 2 kW or less
  3. A single-phase motor whose supply-side circuit breaker is rated 20 A or less
  4. A motor in a place that an operator checks from time to time
AnswerC. A single-phase motor whose supply-side circuit breaker is rated 20 A or less

Article 153(iii) makes an exception for a single-phase motor whose supply-side overcurrent device is rated 15 A or less (20 A or less for a circuit breaker). For the option with a three-phase motor, the exception does not apply because the motor is three-phase. The option "2 kW or less" is wrong: the output exception is 0.2 kW or less. The option about an operator checking from time to time is wrong: the exception is for a motor placed where an operator can watch it at all times while it runs.

Q16 | How fluorescent lamps work

Which correctly describes how a fluorescent lamp (蛍光灯) produces light?

  1. It heats a filament until it glows
  2. It passes current through a semiconductor
  3. It lights a filament inside halogen gas
  4. Ultraviolet light from a discharge in mercury vapour is turned into visible light by a phosphor
AnswerD. Ultraviolet light from a discharge in mercury vapour is turned into visible light by a phosphor

A fluorescent lamp makes ultraviolet light by a discharge in mercury vapour, and the phosphor (蛍光体) inside the tube turns it into visible light. Heating a filament is an incandescent bulb, halogen gas is a halogen bulb, and a semiconductor is how an LED works.

Q17 | Role of the ballast

What is the main role of the ballast (安定器) used with a fluorescent lamp?

  1. To limit the discharge current to a steady level
  2. To convert AC to DC so the lamp lasts longer
  3. To detect earth leakage and cut the circuit
  4. To switch the light on automatically when it gets dark
AnswerA. To limit the discharge current to a steady level

A discharge lets more current flow as current increases, so the ballast limits the current. AC-to-DC power circuits are a feature of LED fixtures, cutting the circuit on leakage is an earth leakage breaker, and switching on in the dark is an automatic light switch.

Q18 | Inverter-type fluorescent lamps

Compared with the glow-starter type (点灯管式), which is a feature of an inverter-type (high-frequency) fluorescent lamp?

  1. It takes a long time to light
  2. It flickers more
  3. It lights at mains frequency, so the circuit is simple
  4. It flickers less and is more efficient
AnswerD. It flickers less and is more efficient

An inverter-type lamp uses an electronic circuit to raise the frequency above mains frequency (50/60 Hz), so it flickers less, is more efficient and lights quickly. Slow lighting and more flicker are the opposite of the comparison. Lighting at mains frequency is not the inverter type.

Q19 | Features of LED lighting

Which is a feature of LED lighting?

  1. It stops working when its filament breaks
  2. It has high luminous efficacy and uses no mercury
  3. It needs mercury vapour to light
  4. It lights by passing AC directly through the light-emitting element
AnswerB. It has high luminous efficacy and uses no mercury

An LED is a semiconductor light-emitting element with high efficacy and no mercury. Filaments are in incandescent bulbs, and mercury vapour is used in fluorescent lamps. LEDs light on DC, so the fixture contains a power circuit that converts AC to DC.

Q20 | Rules on fluorescent lamps

Under the Minamata Convention, which statement matches the Ministry of the Environment's (環境省) explanation of the rules on general-lighting fluorescent lamps (as of October 2026)?

  1. Using fluorescent lamps will be banned from 2026
  2. All straight-tube lamps are banned from manufacture and import/export from 1 January 2026
  3. Manufacture and import/export are banned; use, sale and purchase are not
  4. Compact self-ballasted (bulb-type) fluorescent lamps are not covered
AnswerC. Manufacture and import/export are banned; use, sale and purchase are not

The Ministry explains that only manufacture and import/export are banned; use, sale and purchase are not. Straight tubes are banned from 1 January 2028 (from 1 January 2027 for those using mainly halophosphate phosphor), not 2026. Bulb-type lamps are covered from 1 January 2026 (over 30 W from 1 January 2027).

Q21 | Switching from three places

To switch one light on and off from three places, which combination of switches is needed?

  1. Two 3-way switches and one 4-way switch
  2. Three 3-way switches
  3. Two 4-way switches and one 3-way switch
  4. Three single-pole switches
AnswerA. Two 3-way switches and one 4-way switch

Place two 3-way switches (3路スイッチ) at the ends and (3 − 2) = 1 four-way switch (4路スイッチ) between them. Three 3-way switches alone cannot do it. A 4-way switch is not used at the ends. Three single-pole switches do not let each place turn the light on and off independently.

Q22 | Switching from four places

To switch one light from four places, how many 4-way switches are needed?

  1. 1
  2. 4
  3. 3
  4. 2
AnswerD. 2

You need two 3-way switches plus (n − 2) 4-way switches. With n = 4, that is two 4-way switches. One is for three places; three or four wrongly assume no 3-way switches are used.

Q23 | Locator lamp

When does the lamp of a switch with a locator lamp (位置表示灯) light?

  1. When the switch is on
  2. When the switch is off
  3. When overcurrent flows to the load
  4. When earth leakage occurs
AnswerB. When the switch is off

The locator lamp is connected in parallel with the switch contacts, so it lights when the contacts are open (off) and shows where the switch is in the dark. A lamp that lights when on is a pilot (confirmation) lamp (確認表示灯). It does not signal overcurrent or leakage.

Q24 | Pilot lamp

You want to check at the switch whether a ventilation fan in another place is running. Which switch is suitable?

  1. A switch with a locator lamp
  2. A 4-way switch
  3. A switch with a pilot (confirmation) lamp
  4. An automatic light switch
AnswerC. A switch with a pilot (confirmation) lamp

A pilot lamp (確認表示灯) is in parallel with the load and lights while the switch is on and the load is running. A locator lamp lights when off, so it cannot show operation. A 4-way switch is for switching from three or more places, and an automatic light switch turns on and off by brightness.

Q25 | Automatic light switch

What does an automatic light switch (自動点滅器) do?

  1. Turns off automatically after a set time
  2. Turns on automatically when a person comes near
  3. Changes the brightness smoothly
  4. Turns on when it gets dark and off when it gets light
AnswerD. Turns on when it gets dark and off when it gets light

An automatic light switch senses the surrounding brightness: it turns on in the dark and off in daylight, and is used for outdoor lights. Turning off after a set time is a timer switch, changing brightness is a dimmer, and turning on when someone approaches is a motion-sensor device, which is different.

Q26 | Earth leakage breaker

Which device is meant to detect an earth fault (地絡, leakage) and cut the circuit automatically?

  1. Earth leakage circuit breaker
  2. Thermal overload relay
  3. Power-factor capacitor
  4. 3-way switch
AnswerA. Earth leakage circuit breaker

An earth leakage circuit breaker (漏電遮断器) detects the difference between outgoing and returning current (the leaked current) and cuts the circuit. A thermal relay detects motor overload, a capacitor improves power factor, and a 3-way switch is for switching from two places.

Q27 | 2P1E and 2P2E

In a single-phase three-wire distribution board, which circuit breaker is suitable for a 200 V branch circuit?

  1. 2P1E (2 poles, 1 overcurrent element)
  2. 1P1E (1 pole, 1 element)
  3. 2P2E (2 poles, 2 overcurrent elements)
  4. A switch with no overcurrent element
AnswerC. 2P2E (2 poles, 2 overcurrent elements)

In a 200 V circuit both wires are ungrounded, so a 2P2E breaker with overcurrent elements on both poles is used. With a 2P1E, if the wire without an element faults to earth, that current does not pass the element and is not detected. A 1P1E opens only one wire, and a switch without elements gives no overcurrent protection.

Q28 | Locking receptacle

Which describes a locking (抜け止め形) receptacle?

  1. The plug cannot be pulled out after it is inserted and turned
  2. It is for outdoor places exposed to rain
  3. It has a screw terminal for an earth wire
  4. It is for places with flammable gas
AnswerA. The plug cannot be pulled out after it is inserted and turned

A locking receptacle holds the plug after you insert and turn it. Rain-exposed places use a rainproof type (防雨形), a screw terminal for an earth wire is an earthing-terminal type (接地端子付), and places with flammable gas use an explosion-proof type (防爆形, marked EX).

Q29 | Earthing-pole receptacle

Which describes a receptacle with an earthing pole (接地極付コンセント)?

  1. It has only a screw terminal for an earth wire
  2. The plug locks when inserted and turned
  3. It has a slot for the earthing pin of an earthing-type plug
  4. It detects leakage and cuts the circuit
AnswerC. It has a slot for the earthing pin of an earthing-type plug

A receptacle with an earthing pole has a slot that receives the earthing pin of an earthing-type plug. One with only a screw terminal is an earthing-terminal type (接地端子付). Locking when turned is the locking type. Detecting leakage and cutting the circuit is the job of an earth leakage breaker, not this receptacle.

Q30 | Specified electrical products

Under the Electrical Appliances and Materials Safety Act (電気用品安全法), which range of circuit breakers (配線用遮断器) is a specified electrical product (特定電気用品), according to METI?

  1. Rated current of 30 A or less
  2. Rated current of 200 A or more
  3. None, regardless of rated current
  4. Rated current of 100 A or less (for motors, applicable motor 12 kW or less)
AnswerD. Rated current of 100 A or less (for motors, applicable motor 12 kW or less)

METI's list covers circuit breakers and earth leakage breakers with a rated current of 100 A or less (for motor use, applicable motor rating 12 kW or less). 30 A or less is the range for switches. 200 A or more and 'none' are wrong.

Practice: answer the questions on this page

This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.

* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.