In a single-phase three-wire 100/200 V system, what is the voltage between the two outer wires?
100 V
141 V
173 V
200 V
AnswerD. 200 V
In a single-phase three-wire system, the voltage between an outer wire and the neutral is 100 V, and between the two outer wires it is 200 V. 141 V is 100×√2 and 173 V is 100×√3; neither is the outer-to-outer voltage here. 100 V is the outer-to-neutral voltage.
Q2 | Three-phase three-wire system
Which statement about a 200 V three-phase three-wire system is correct?
The voltage between any two of the three wires is 200 V
There are four wires, one of which is always a neutral
The voltage between any two wires is 200÷√3 V
It is mainly used for household 100 V outlets
AnswerA. The voltage between any two of the three wires is 200 V
A 200 V three-phase three-wire system uses three wires, and the voltage between any two of them is 200 V. There are three wires and no neutral as in the single-phase three-wire system. 200÷√3 (about 115 V) is not a line-to-line voltage. It is mainly used for motors (power loads) in factories; household 100 V outlets are fed from single-phase circuits.
Q3 | Voltage to be maintained (100 V)
Under the Ordinance for Enforcement of the Electricity Business Act (電気事業法施行規則), what range must be maintained at the supply point for a standard voltage of 100 V (as of October 2026)?
90 V to 110 V
95 V to 107 V
97 V to 103 V
101 V to 107 V
AnswerB. 95 V to 107 V
Article 38 of the Ordinance requires a value "not deviating more than 6 V above or below 101 V" for a standard voltage of 100 V. 101−6=95 and 101+6=107, so the range is 95 V to 107 V. 90–110 V is ±10 V around 100 V and 97–103 V is ±3 V around 100 V; neither is the standard. 101–107 V looks only at the upper side.
Q4 | Voltage to be maintained (200 V)
Under the Ordinance for Enforcement of the Electricity Business Act (電気事業法施行規則), what range must be maintained for a standard voltage of 200 V (as of October 2026)?
180 V to 220 V
190 V to 210 V
182 V to 222 V
196 V to 208 V
AnswerC. 182 V to 222 V
Article 38 requires a value "not deviating more than 20 V above or below 202 V" for 200 V. 202−20=182 and 202+20=222. 180–220 V wrongly centres on 200 V, and 190–210 V and 196–208 V use the wrong width.
Q5 | Neutral current when balanced
Resistive loads of 10 A on both the upper and lower sides
In the single-phase three-wire circuit shown, 10 A flows in each of the upper and lower 100 V loads (both resistive). What current flows in the neutral?
0 A
5 A
10 A
20 A
AnswerA. 0 A
The neutral current is the difference between the upper and lower currents: 10−10=0 A. When the loads are balanced, no current flows in the neutral. 20 A adds the currents, 10 A just repeats one side, and 5 A halves it; all are wrong.
Q6 | Neutral current when unbalanced
In a single-phase three-wire 100/200 V system, 15 A flows in the upper 100 V load and 9 A in the lower 100 V load (both resistive). What current flows in the neutral?
24 A
6 A
12 A
0 A
AnswerB. 6 A
With resistive loads, the neutral current is the difference: 15−9=6 A. 24 A is the sum, 12 A is the average, and 0 A applies only when balanced.
Q7 | Broken neutral
The neutral is broken at the X mark
In the single-phase three-wire 100/200 V circuit shown, a resistive load rated 100 V 200 W is on the upper side and one rated 100 V 600 W is on the lower side. If the neutral breaks at the X mark, what voltage is applied to the 200 W load? Assume the load resistances do not change and the outer-to-outer voltage is 200 V.
50 V
100 V
150 V
200 V
AnswerC. 150 V
Resistance R=V²/P: the 200 W load is 100²÷200=50 Ω and the 600 W load is 100²÷600≈16.7 Ω. With the neutral broken, the two are in series across 200 V. Current = 200÷(50+16.7)=3 A, so the 200 W load gets 3×50=150 V. 50 V is the voltage on the 600 W load, 100 V is the voltage before the break, and 200 V is the total. The danger is that the lower-power load receives the higher voltage.
Q8 | Three-wire system and loss
Power is sent to the same resistive load using wires of the same size. If a single-phase two-wire 100 V supply is changed to a balanced single-phase three-wire 100/200 V supply (load split in half), by what factor does the line power loss change?
1/2
2
No change
1/4
AnswerD. 1/4
In two-wire with current I, the loss is 2I²r. In balanced three-wire, the outer-wire current is I/2 and the neutral carries 0, so the loss is 2×(I/2)²×r=I²r/2. I²r/2 ÷ 2I²r = 1/4. Loss is proportional to the square of current, so halving the current gives 1/4, not 1/2. "2" and "No change" miss the reduced current.
Q9 | Voltage drop, single-phase two-wire
In a single-phase two-wire circuit, each wire has a resistance of 0.1 Ω and the load current is 20 A (resistive load). What is the voltage drop in the line?
2 V
4 V
8 V
0.2 V
AnswerB. 4 V
In two-wire, current flows in both the outgoing and return wires, so v=2Ir=2×20×0.1=4 V. 2 V counts only one wire, 8 V counts four wires, and 0.2 V forgets to multiply by the current (2×0.1).
Q10 | Load voltage, two-wire
In a single-phase two-wire circuit, the source voltage is 104 V, each wire has a resistance of 0.15 Ω, and the load current is 10 A (resistive). What voltage is applied to the load?
102.5 V
104 V
98 V
101 V
AnswerD. 101 V
The drop is 2Ir=2×10×0.15=3 V, so the load voltage is 104−3=101 V. 102.5 V subtracts only one wire (1.5 V), 104 V ignores the drop, and 98 V counts the drop twice (104−6).
Q11 | Line length and voltage drop
In a single-phase two-wire circuit, the distance from source to load is 25 m, the wire resistance is 8 Ω per km (per wire), and the load current is 15 A (resistive). What is the voltage drop?
6 V
3 V
0.6 V
12 V
AnswerA. 6 V
Resistance of one wire: r=8×25÷1000=0.2 Ω. For two-wire, v=2Ir=2×15×0.2=6 V. 3 V counts one wire only, 12 V doubles the round trip again, and 0.6 V comes from a unit-conversion slip (taking r=0.02 Ω).
Q12 | Power loss, two-wire
In a single-phase two-wire circuit, each wire has a resistance of 0.2 Ω and the load current is 10 A. What is the power loss in the line?
20 W
4 W
40 W
80 W
AnswerC. 40 W
Loss P=2I²r=2×10²×0.2=40 W. 20 W counts one wire, 80 W counts four, and 4 W forgets to square the current (2×10×0.2).
Q13 | Voltage drop, three-phase three-wire
In a three-phase three-wire circuit, each wire has a resistance of 0.15 Ω and the line current is 20 A (resistive load). Which is closest to the line-to-line voltage drop?
3.0 V
5.2 V
6.0 V
9.0 V
AnswerB. 5.2 V
For three-phase three-wire, v=√3·Ir=1.73×20×0.15≈5.2 V. 3.0 V is Ir (one wire), 6.0 V uses the two-wire formula 2Ir, and 9.0 V uses 3Ir.
Q14 | Power loss, three-phase three-wire
In a three-phase three-wire circuit, each wire has a resistance of 0.1 Ω and the line current is 10 A. What is the power loss in the line?
17 W
20 W
30 W
10 W
AnswerC. 30 W
Each of the three wires loses I²r, so P=3I²r=3×10²×0.1=30 W. 17 W is √3·I²r, 20 W is the two-wire 2I²r, and 10 W is one wire only. Count losses by the number of wires; √3 is not used here.
Q15 | Load voltage, balanced three-wire
In a single-phase three-wire 100/200 V system, the source voltage between each outer wire and the neutral is 105 V and each wire has a resistance of 0.1 Ω. 20 A flows in each of the upper and lower 100 V loads (balanced, resistive). What voltage is applied to the upper load?
101 V
104 V
105 V
103 V
AnswerD. 103 V
Since the loads are balanced, no current flows in the neutral, and the drop is one outer wire: Ir=20×0.1=2 V. The load voltage is 105−2=103 V. 101 V subtracts 2Ir as in two-wire, 105 V ignores the drop, and 104 V halves the current.
Q16 | Load voltage, unbalanced three-wire
20 A on the upper side, 10 A on the lower side; each wire is 0.1 Ω
In the single-phase three-wire circuit shown, the source voltage between each outer wire and the neutral is 105 V and every wire has a resistance of 0.1 Ω. 20 A flows in upper Load 1 and 10 A in lower Load 2 (resistive). What voltage is applied to Load 1?
102 V
103 V
104 V
101 V
AnswerA. 102 V
The neutral carries the difference, 20−10=10 A. Load 1 voltage = 105 − (outer-wire drop 20×0.1) − (neutral drop 10×0.1) = 105−2−1 = 102 V. 103 V forgets the neutral drop, 101 V assumes 20 A in the neutral too, and 104 V forgets the outer-wire drop. (Load 2 gets 105−1+1=105 V.)
Q17 | Allowable current of a feeder with motors
A low-voltage feeder (幹線) supplies motors with a total rated current of 40 A and electric heaters with a total rated current of 15 A (ignore demand factor and power factor). According to Article 148 of the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), what is the minimum allowable current of the feeder wire?
65 A
55 A
59 A
68.75 A
AnswerA. 65 A
The motors' total (40 A) is larger than the heaters' total (15 A) and is 50 A or less, so multiply the motor total by 1.25 and add the heater total: 15 + 1.25 × 40 = 15 + 50 = 65 A. 55 A simply adds them (ignoring motor starting current), 59 A uses the factor 1.1 that applies only above 50 A (15 + 44), and 68.75 A wrongly applies 1.25 to the heaters as well (55 × 1.25).
Q18 | Position of a branch-circuit breaker
The overcurrent breaker protecting a low-voltage feeder is rated 100 A. A branch circuit is taken from this feeder, and its overcurrent breaker is installed 6 m (wire length) from the branch point. According to Article 149 of the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), what is the minimum allowable current of the wire from the branch point to this breaker?
25 A
55 A
100 A
35 A
AnswerD. 35 A
As a rule, a branch-circuit breaker must be within 3 m of the branch point. It may be farther if the wire is 8 m or shorter and its allowable current is at least 35% of the rating of the breaker protecting the feeder: 100 × 0.35 = 35 A. 55 A (55%) is required only when there is no length limit, not for 6 m. 100 A is just the breaker rating and is not a rule value. 25 A is below 35%.
Q19 | Purpose of allowable current
Which is the main reason an allowable current (許容電流) is set for a wire?
To prevent the wire from overheating and damaging its insulation
To keep the voltage drop constant
To keep the supports from breaking under the wire’s weight
To keep the current within the range the watt-hour meter can measure
AnswerA. To prevent the wire from overheating and damaging its insulation
Current makes a wire heat up; if it gets too hot, the insulation is damaged and short circuits or fires can result. The allowable current is the limit that prevents this. Voltage drop depends on length and current and is not held constant by the allowable current. Wire weight and meter range are not the reason.
Q20 | Number of wires in a conduit
When more insulated wires are put in the same conduit, how is the allowable current per wire treated?
It is increased in proportion to the number of wires
It does not change
It is increased by multiplying by a factor greater than 1
It is reduced by multiplying by a factor smaller than 1
AnswerD. It is reduced by multiplying by a factor smaller than 1
When many wires share a conduit, heat builds up, so the original allowable current is multiplied by a current reduction factor (電流減少係数) smaller than 1. The more wires, the smaller the factor. Increasing it or leaving it unchanged ignores the heat build-up.
Q21 | Allowable current in a conduit
Three 600 V PVC-insulated wires (600Vビニル絶縁電線, annealed copper) 2.0 mm in diameter are installed in the same metal conduit. The ambient temperature is 30 °C or lower. According to Article 146 of the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), what is the allowable current of each wire?
18.9 A
24.5 A
33.6 A
35 A
AnswerB. 24.5 A
The allowable current of 2.0 mm copper wire is 35 A (Table 146-1). At 30 °C or lower the temperature correction factor is 1, and the current reduction factor for three or fewer wires is 0.70 (Table 146-4), so 35 × 1 × 0.70 = 24.5 A. 18.9 A is the value for 1.6 mm wire (27 A × 0.70), 33.6 A is for 2.6 mm wire (48 A × 0.70), and 35 A forgets the reduction factor.
Q22 | Ambient temperature and allowable current
Which statement is correct about the allowable current of a wire installed where the surrounding (ambient) temperature is high?
The higher the ambient temperature, the smaller the allowable current
The higher the ambient temperature, the larger the allowable current
Ambient temperature has nothing to do with allowable current
A high ambient temperature makes the current reduction factor greater than 1
AnswerA. The higher the ambient temperature, the smaller the allowable current
At a higher ambient temperature, heat escapes less easily and the insulation heats up more, so the allowable current becomes smaller. Under Article 146 of the Interpretation, the allowable current of PVC-insulated wire is multiplied by the correction factor √((60 − θ) ÷ 30) (θ = ambient temperature, taken as 30 at 30 °C or below), which falls below 1 above 30 °C. "Larger" and "no relation" ignore heat dissipation. The current reduction factor depends on the number of wires and is never greater than 1.
Q23 | Cross-sectional area
Which is closest to the cross-sectional area of a round solid wire 2.0 mm in diameter?
2.0 mm²
6.28 mm²
3.14 mm²
12.6 mm²
AnswerC. 3.14 mm²
Area = πr², and the radius is half the diameter, 1.0 mm: π×1.0²≈3.14 mm². 12.6 mm² uses the diameter as the radius (π×2.0²), 6.28 mm² uses the circumference formula (2πr), and 2.0 mm² simply reuses the diameter.
Q24 | Choosing the wire size
Three 600 V PVC-insulated wires (solid annealed copper) are installed in the same metal conduit for a circuit with a load current of 25 A. The ambient temperature is 30 °C or lower. Using the allowable currents in Article 146 of the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), which is the thinnest wire whose allowable current is at least the load current?
3.2 mm diameter
2.6 mm diameter
2.0 mm diameter
1.6 mm diameter
AnswerB. 2.6 mm diameter
With three wires in the conduit, the current reduction factor is 0.70. 1.6 mm: 27 × 0.70 = 18.9 A; 2.0 mm: 35 × 0.70 = 24.5 A; 2.6 mm: 48 × 0.70 = 33.6 A; 3.2 mm: 62 × 0.70 = 43.4 A. The thinnest wire with at least 25 A is 2.6 mm. 2.0 mm gives 24.5 A, just short (comparing 35 A without the factor would wrongly select it). 1.6 mm is also too small. 3.2 mm would work but is not the thinnest.
Q25 | Effect of a thicker wire
Keeping the same length and material, which change is correct when a wire is replaced with a thicker one (larger cross-sectional area)?
Resistance increases, and the voltage drop increases
Resistance decreases, and the allowable current decreases
Resistance decreases, and the voltage drop and power loss decrease
Resistance is unchanged; only the allowable current increases
AnswerC. Resistance decreases, and the voltage drop and power loss decrease
Resistance is inversely proportional to area, so a thicker wire has lower resistance. At the same current, both voltage drop (IR) and power loss (I²R) fall, and the allowable current rises. The other options state the wrong direction or no change in resistance.
Q26 | What a branch circuit is
Which is the correct description of a branch circuit (分岐回路)?
The wire from the utility pole to the building’s service entrance
The line from the service entrance to the distribution board carrying the whole building’s current
A circuit that branches off the feeder and runs to loads such as lights and outlets
The winding inside a transformer that changes the voltage
AnswerC. A circuit that branches off the feeder and runs to loads such as lights and outlets
A branch circuit branches off the feeder (幹線) and runs to electrical equipment such as lights and outlets. Article 63 of the Ministerial Ordinance on Technical Standards (電気設備に関する技術基準を定める省令) describes it as a low-voltage circuit branching from the low-voltage feeder to equipment. The pole-to-entrance wire is the service drop (引込線), the entrance-to-board line is the feeder, and a transformer winding is not a wiring circuit.
Q27 | Feeder current
A single-phase two-wire 100 V feeder supplies 1,500 W, 1,000 W and 500 W heaters (resistive loads) at the same time. What current flows in the feeder?
15 A
20 A
45 A
30 A
AnswerD. 30 A
I=P÷V: 15 A + 10 A + 5 A = 30 A. All load currents add up in the feeder. 15 A counts only the largest load, 20 A adds only the 1,500 W and 500 W heaters, and 45 A counts the 1,500 W heater twice.
Q28 | Wire and outlets for a branch circuit
A branch circuit (not one supplying only motors) is protected by a 30 A molded-case circuit breaker (配線用遮断器). According to Article 149 of the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), which combination of wire size (annealed copper) and outlet (コンセント) is acceptable?
2.0 mm wire, 20 A outlet
2.6 mm wire, 30 A outlet
2.6 mm wire, 15 A outlet
1.6 mm wire, 30 A outlet
AnswerB. 2.6 mm wire, 30 A outlet
For a breaker rated over 20 A up to 30 A, the wire must be at least 2.6 mm in diameter (Table 149-1) and the outlet must be rated 20 A to 30 A, excluding outlets that accept plugs rated below 20 A (Table 149-3). So "2.6 mm, 30 A" is acceptable. 2.0 mm and 1.6 mm wires are too thin for a 30 A breaker, and a 15 A outlet is rated too low.
Q29 | Earth-leakage breaker
Which describes what an earth-leakage circuit breaker (漏電遮断器) does?
It opens the circuit only when the current exceeds its rating
It raises the voltage when the voltage becomes low
It detects a ground fault (leakage) and opens the circuit
It diverts lightning surges to the ground
AnswerC. It detects a ground fault (leakage) and opens the circuit
An earth-leakage breaker detects a ground fault—current leaving its proper path and flowing to the ground—and opens the circuit. Article 15 of the Ministerial Ordinance requires measures such as ground-fault breakers to prevent damage, electric shock and fire from ground faults. Opening on overcurrent is the job of an overcurrent breaker. It neither raises voltage nor acts as a surge arrester (避雷器).
Q30 | Breaker rated too high
A branch circuit built with wire whose allowable current is 20 A is fitted with a 40 A molded-case circuit breaker. Which is the most likely result?
The breaker trips often during normal use
The voltage at the load doubles
The power loss in the wire becomes zero
The breaker may not trip even if the wire overheats, creating a fire risk
AnswerD. The breaker may not trip even if the wire overheats, creating a fire risk
The breaker exists to protect the wire. A 40 A breaker on wire rated 20 A may not trip when the current exceeds 20 A and the wire overheats, which can cause a fire. Frequent tripping happens when the breaker is too small. The breaker rating does not double the voltage or eliminate loss. Table 149-1 of the Interpretation requires copper wire of at least 8 mm² for a branch circuit with a 40 A breaker.
Practice: answer the questions on this page
This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.
* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.