Q1 | Wiring methods for high-voltage indoor wiring
Which method does the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈) allow for high-voltage indoor wiring?
Metal conduit wiring
Cable wiring
Rigid PVC conduit wiring
Metal duct wiring
AnswerB. Cable wiring
Article 168 allows high-voltage indoor wiring only by insulator (knob) wiring in dry, exposed places, or by cable wiring. Metal conduit, PVC conduit and metal duct wiring are low-voltage indoor wiring methods and are not listed for high voltage.
Q2 | Grounding of conduit for high-voltage cable
High-voltage indoor wiring is installed by cable wiring. As a rule (with no contact-protection measures), which class of grounding is required for the metal parts of the conduit that holds the cable?
Class D grounding
Class C grounding
Class B grounding
Class A grounding
AnswerD. Class A grounding
Article 168 requires Class A grounding for metal parts of protective conduit, metal junction boxes and metal cable sheaths in high-voltage cable wiring. Class D is allowed only when contact-protection measures are taken. Class C is for enclosures of low-voltage equipment over 300 V, and Class B is for the low-voltage side of a transformer that couples high and low voltage, so they are wrong here.
Q3 | Separation of high-voltage indoor wiring
When high-voltage indoor wiring comes close to low-voltage indoor wires or water pipes, what separation is required if no barrier or fire-resistant conduit is used (the low-voltage wire is not bare)?
15 cm
5 cm
30 cm
1 m
AnswerA. 15 cm
Article 168(2) requires at least 15 cm between high-voltage indoor wiring and other indoor wires, water pipes or gas pipes (30 cm if the other is a bare low-voltage wire on insulators). 5 cm is the clearance between a high-voltage wire and the building in insulator wiring, 30 cm applies to bare wires, and 1 m is the clearance of arcing high-voltage switches from combustibles, so none fits here.
Q4 | Spacing in high-voltage insulator wiring
High-voltage indoor wiring is installed by insulator (knob) wiring. Which pair gives the correct spacing between wires and clearance from the building structure?
Wires 6 cm or more; structure 2.5 cm or more
Wires 10 cm or more; structure 10 cm or more
Wires 8 cm or more; structure 5 cm or more
Wires 15 cm or more; structure 8 cm or more
AnswerC. Wires 8 cm or more; structure 5 cm or more
Article 168(1)(ii) requires at least 8 cm between wires and at least 5 cm between a wire and the building structure. The pairs 6 cm/2.5 cm, 10 cm/10 cm and 15 cm/8 cm do not match (15 cm is the separation from other wires and pipes).
Q5 | Burial depth for direct burial
A high-voltage underground line is laid by direct burial. Where it may be under pressure from vehicles or other heavy objects, what is the minimum burial depth as a rule?
1.2 m
0.3 m
0.6 m
2.0 m
AnswerA. 1.2 m
Article 120(4) requires at least 1.2 m where vehicles or heavy objects may press on the line, and at least 0.6 m elsewhere. 0.6 m is the value for other places; 0.3 m and 2.0 m are not burial depths in Article 120.
Q6 | Fence around high-voltage equipment
Outside a factory premises, high-voltage equipment is protected by a fence 2 m high. What is the minimum distance from the fence to the live parts of the equipment?
1 m
2 m
2.5 m
3 m
AnswerD. 3 m
Article 21 requires the fence height plus the distance from the fence to the live parts to be at least 5 m. 5 m − 2 m = 3 m. With 1 m the sum is 3 m, with 2 m it is 4 m, and with 2.5 m it is 4.5 m, all short of 5 m.
Q7 | Clearance for arcing devices
A high-voltage switch that produces an arc when it operates is installed without a fire-resistant enclosure. How far must it be from a wooden wall or ceiling?
0.5 m
1 m
2 m
3 m
AnswerB. 1 m
Article 23 requires arcing switches and similar devices to be at least 1 m from combustibles for high voltage, and as a rule 2 m for extra-high voltage up to 35,000 V. 2 m is the extra-high-voltage value; 0.5 m and 3 m are not in Table 23-1.
Q8 | Grounding the enclosure of high-voltage equipment
Which class of grounding is required for the metal enclosure of a high-voltage transformer?
Class A grounding
Class B grounding
Class C grounding
Class D grounding
AnswerA. Class A grounding
Article 29 (Table 29-1) requires Class D for low-voltage equipment up to 300 V, Class C for low voltage over 300 V, and Class A for high or extra-high voltage. Class B is not for enclosures; it is applied to the low-voltage neutral (or a terminal) of a transformer coupling high and low voltage. Classes C and D are for low-voltage equipment enclosures.
Q9 | Values for Class A grounding
Which pair gives the grounding resistance of Class A grounding and the size of the earthing conductor when annealed copper wire is used (excluding flexible parts of movable equipment)?
100 Ω or less; 1.6 mm diameter or more
10 Ω or less; 1.6 mm diameter or more
100 Ω or less; 2.6 mm diameter or more
10 Ω or less; 2.6 mm diameter or more
AnswerD. 10 Ω or less; 2.6 mm diameter or more
Article 17(1) sets Class A grounding at 10 Ω or less, with an annealed copper earthing conductor of at least 2.6 mm diameter (or a corrosion-resistant metal wire with tensile strength of at least 1.04 kN). 100 Ω is the Class D value and 1.6 mm is the conductor size for Classes C and D, so pairs containing them are wrong.
Q10 | Protecting a Class A earthing conductor
A Class A earthing conductor is installed where people may touch it. Which range of the conductor must be covered with plastic conduit or similar?
From 30 cm below ground to 1 m above ground
From 75 cm below ground to 2 m above ground
From 60 cm below ground to 2.5 m above ground
From 1 m below ground to 3 m above ground
AnswerB. From 75 cm below ground to 2 m above ground
Article 17(1)(iii) requires the earth electrode to be buried at least 75 cm deep and the conductor from 75 cm below ground to 2 m above ground to be covered with plastic conduit (excluding PVC conduit thinner than 2 mm and CD pipe) or similar. The other ranges do not match (60 cm is easily confused with the '60 cm above ground' in the rule on using insulated wire for the conductor).
Q11 | Grounding the secondary of instrument transformers
Which class of grounding is required for the secondary circuit of a high-voltage instrument transformer (VT or CT)?
Class A grounding
Class B grounding
Class C grounding
Class D grounding
AnswerD. Class D grounding
Article 28 requires Class D grounding on the secondary circuit of a high-voltage instrument transformer, and Class A for an extra-high-voltage one. Class A is the extra-high-voltage case, Class B is for the low-voltage side of a transformer coupling high and low voltage, and Class C is for enclosures of low-voltage equipment over 300 V.
Q12 | Class B grounding resistance (no automatic cutoff)
Class B grounding is applied to the low-voltage side of a transformer coupling high and low voltage. The one-line ground-fault current Ig on the high-voltage side is 5 A, and there is no device that automatically cuts the high-voltage circuit when the windings make contact. What is the maximum grounding resistance?
10 Ω
60 Ω
120 Ω
30 Ω
AnswerD. 30 Ω
With no cutoff device, Article 17(2) (Table 17-1) uses 150/Ig: 150 ÷ 5 = 30 Ω. 60 Ω would come from 300/Ig (cutoff in more than 1 s up to 2 s) and 120 Ω from 600/Ig (1 s or less). 10 Ω is the Class A value and has nothing to do with this calculation.
Q13 | Class B grounding resistance (cutoff within 1 s)
On a circuit with a one-line ground-fault current Ig of 4 A on the high-voltage side, there is a device that automatically cuts the high-voltage circuit within 1 second when, after the windings make contact, the low-voltage circuit's voltage to earth exceeds 150 V. What is the maximum resistance for the Class B grounding?
37.5 Ω
75 Ω
150 Ω
600 Ω
AnswerC. 150 Ω
Because the cutoff time is 1 s or less, use 600/Ig from Article 17(2) (Table 17-1): 600 ÷ 4 = 150 Ω. 37.5 Ω comes from 150/Ig (no cutoff device) and 75 Ω from 300/Ig (more than 1 s up to 2 s). 600 Ω is just the numerator, not divided by Ig.
Q14 | Installing surge arresters
At a customer supplied from a high-voltage overhead line, from what received power is a surge arrester required at the service entrance, and which class of grounding does it need?
50 kW or more; Class D grounding
500 kW or more; Class C grounding
50 kW or more; Class B grounding
500 kW or more; Class A grounding
AnswerD. 500 kW or more; Class A grounding
Article 37 requires a surge arrester at the service entrance of a customer receiving 500 kW or more from a high-voltage overhead line, and requires Class A grounding for arresters on high-voltage and extra-high-voltage circuits. 50 kW is not in the rule, and Classes B, C and D are the wrong classes for an arrester.
Q15 | Hanger spacing for overhead high-voltage cable
A high-voltage overhead service line uses cable supported from a messenger wire by hangers. What is the maximum spacing of the hangers?
20 cm
1 m
50 cm
2 m
AnswerC. 50 cm
Article 117 says a cable service line follows Article 67, and Article 67 limits hanger spacing to 50 cm for high-voltage overhead cable. 20 cm is the pitch for spirally wrapping metal tape, and 2 m is the support spacing for low-voltage cable fixed along a building. 1 m is not in Article 67 (in Article 164 it is the support spacing for cabtyre cable).
Q16 | Finding the maximum operating voltage
What is the maximum operating voltage (最大使用電圧) of a high-voltage circuit with a nominal voltage of 6,600 V?
6,600 V
6,900 V
7,590 V
9,900 V
AnswerB. 6,900 V
Under Article 1 (Table 1-1), for circuits over 1,000 V and under 500,000 V the maximum operating voltage is the nominal voltage × 1.15/1.1: 6,600 × 1.15 ÷ 1.1 = 6,900 V. 6,600 V has no factor applied, 7,590 V uses only 1.15 (the factor for 1,000 V or less), and 9,900 V is 1.5 times the nominal voltage.
Q17 | AC test voltage for a high-voltage circuit
A dielectric withstand test (絶縁耐力試験) is done with AC on a high-voltage circuit with a nominal voltage of 6,600 V. What test voltage is applied between the circuit and earth?
10,350 V
9,900 V
8,625 V
20,700 V
AnswerA. 10,350 V
The maximum operating voltage is 6,600 × 1.15 ÷ 1.1 = 6,900 V. Under Article 15 (Table 15-1), an AC circuit with a maximum operating voltage of 7,000 V or less is tested at 1.5 times that: 6,900 × 1.5 = 10,350 V. 9,900 V is 1.5 times the nominal voltage, 8,625 V uses 1.25 times, and 20,700 V is the DC value for cable.
Q18 | DC testing of cable
The dielectric withstand test of a 6,600 V (nominal) high-voltage cable circuit is done with DC. Which test voltage is correct?
10,350 V
13,800 V
20,700 V
16,560 V
AnswerC. 20,700 V
Article 15(ii) allows a cable AC circuit to be tested with a DC voltage twice the Table 15-1 value for 10 minutes. The AC test voltage is 6,900 × 1.5 = 10,350 V, so 10,350 × 2 = 20,700 V. 10,350 V is the AC value unchanged, 13,800 V is twice the maximum operating voltage, and 16,560 V uses 1.6 (the factor for DC testing of rotating machines).
Q19 | Duration of the test voltage
In a dielectric withstand test of a high-voltage circuit, how long must the test voltage be applied according to the Interpretation of the Technical Standards for Electrical Equipment (電気設備の技術基準の解釈)?
1 minute continuously
10 minutes continuously
30 minutes continuously
10 minutes in total (may be split)
AnswerB. 10 minutes continuously
Article 15 requires the circuit to withstand the test voltage applied between the circuit and earth 'continuously for 10 minutes'. 1 minute and 30 minutes are not in the rule, and splitting the time into parts does not meet the 'continuously' condition.
Q20 | Test voltage for a transformer's low-voltage winding
For a 6,600 V / 200 V transformer, what is the dielectric withstand test voltage of the low-voltage winding (nominal 200 V)?
230 V
300 V
500 V
345 V
AnswerC. 500 V
The low-voltage winding's maximum operating voltage is 200 × 1.15 = 230 V. Article 16 (Table 16-1) uses 1.5 times for windings of 7,000 V or less, but not less than 500 V. 230 × 1.5 = 345 V, which is below 500 V, so the test voltage is 500 V. 230 V is just the maximum operating voltage, 345 V forgets the 500 V minimum, and 300 V is 1.5 times the nominal voltage.
Q21 | Test voltage for a high-voltage motor
What AC dielectric withstand test voltage is applied between the windings and earth of a three-phase induction motor with a nominal voltage of 3,300 V?
3,450 V
4,950 V
5,175 V
8,280 V
AnswerC. 5,175 V
The maximum operating voltage is 3,300 × 1.15 ÷ 1.1 = 3,450 V. Article 16(2) (Table 16-2) tests rotating machines of 7,000 V or less at 1.5 times: 3,450 × 1.5 = 5,175 V. 3,450 V is the maximum operating voltage itself, 4,950 V is 1.5 times the nominal voltage, and 8,280 V is the DC test value (1.6 × 5,175 V).
Q22 | Charging current during the test
An AC test voltage of 10,350 V at 60 Hz is applied to a high-voltage cable with a capacitance of 0.3 μF. About how much charging current flows (ignore leakage current)?
0.98 A
0.19 A
2.34 A
1.17 A
AnswerD. 1.17 A
The charging current is I = 2πfCV: I = 2 × 3.14 × 60 × 0.3 × 10⁻⁶ × 10,350 ≈ 1.17 A. 0.98 A is the result for 50 Hz, 0.19 A forgets the 2π factor (60 × 0.3 × 10⁻⁶ × 10,350 ≈ 0.19), and 2.34 A wrongly uses the DC test voltage of 20,700 V. The test transformer needs enough capacity to supply this current (roughly 10,350 V × 1.17 A ≈ 12.1 kVA).
Q23 | Procedure for the withstand test
Which is an appropriate procedure for a dielectric withstand test of high-voltage cable?
Measure insulation resistance only before the test, not after
Measure insulation resistance before and after, and discharge the cable before touching it
Touch the cable right after the test to check its temperature
Apply the test voltage suddenly and remove it immediately
AnswerB. Measure insulation resistance before and after, and discharge the cable before touching it
Insulation resistance is measured before the test so that high voltage is not applied to obviously bad insulation, and after the test to check that the test did not damage it. Cable has large capacitance and keeps a charge, so it must be discharged (for example, with a grounding rod) before touching. Measuring only before cannot find damage from the test, touching without discharging risks electric shock, and Article 15 requires the voltage to be held continuously for 10 minutes, so removing it immediately is wrong.
Q24 | Ground relay and zero-phase CT
Which pair correctly gives the device used with a ground relay (GR) in high-voltage receiving equipment to detect ground faults, and what that device detects?
A zero-phase current transformer (ZCT), detecting zero-phase current
A voltage transformer (VT), detecting line voltage
A current transformer (CT), detecting the load current of one wire
A surge arrester (LA), detecting abnormal voltage
AnswerA. A zero-phase current transformer (ZCT), detecting zero-phase current
A ground relay is combined with a zero-phase current transformer (ZCT), which detects the sum of the currents in the three wires (zero-phase current). Without a ground fault the sum is almost zero; with one, the current flowing to earth appears. A VT transforms voltage for meters, a CT detects load current for devices such as overcurrent relays, and a surge arrester sends abnormal voltage to earth, so none of them detect ground-fault current.
Q25 | What relay testing checks
In testing the protective relays of high-voltage receiving equipment, what is the test that checks that the circuit breaker actually opens when the relay operates?
Interlock (trip) test
Temperature rise test
Continuity test
Dielectric withstand test
AnswerA. Interlock (trip) test
Relay testing checks whether the relay operates at its set value (operating current) and how long it takes (operating time), and then an interlock test checks that the breaker actually opens when the relay operates. A temperature rise test runs equipment to see how hot it gets, a continuity test checks that wiring is connected, and a withstand test checks insulation under high voltage; none of them checks the breaker's operation.
Practice: answer the questions on this page
This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.
* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.