Read the questions and explanations in English. The lectures (explanatory articles) are available in Japanese only.

View the Japanese version (with lectures) →

Q1 | Output of a hydro plant

A hydroelectric plant has a flow rate of 15 m³/s, an effective head of 80 m and an overall turbine-generator efficiency of 80%. What is its output?

  1. 960 kW
  2. 7,526 kW
  3. 9,408 kW
  4. 11,760 kW
AnswerC. 9,408 kW

P = 9.8 × Q × H × η = 9.8 × 15 × 80 × 0.8 = 9,408 kW. 960 kW forgets the gravitational acceleration 9.8, 7,526 kW applies the efficiency twice, and 11,760 kW leaves out the efficiency.

Q2 | Pumped-storage hydro

Which statement correctly describes a pumped-storage power plant (揚水式発電所)?

  1. When power is in surplus, it pumps water from a lower to an upper reservoir, and generates when power is short
  2. It takes river water without storing it and generates according to the flow that arrives
  3. It drives a turbine with hot steam or hot water pumped up from underground
  4. It generates using the difference in water level caused by the tides
AnswerA. When power is in surplus, it pumps water from a lower to an upper reservoir, and generates when power is short

A pumped-storage plant uses surplus electricity to pump water up to the upper reservoir and generates with that water when demand is high, storing energy as height of water. Using river water directly is run-of-river (流込み式), using underground steam is geothermal, and using tides is tidal power; none of these is pumped storage.

Q3 | Types of water turbines

Which water turbine is best suited to a site with a large head of several hundred metres and a relatively small flow?

  1. Propeller turbine
  2. Pelton turbine
  3. Kaplan turbine
  4. Francis turbine
AnswerB. Pelton turbine

The Pelton turbine (an impulse turbine), turned by jets from nozzles striking its buckets, suits high heads. Propeller and Kaplan turbines suit low heads with large flows, and the Francis turbine is a reaction turbine widely used for medium heads.

Q4 | Role of the condenser

Which describes the role of the condenser (復水器) in a steam power plant?

  1. Burning fuel to turn feed water into steam
  2. Raising the pressure of water sent to the boiler
  3. Further heating steam before it goes to the turbine
  4. Cooling the steam leaving the turbine back into water
AnswerD. Cooling the steam leaving the turbine back into water

The condenser cools the steam leaving the turbine back into water and keeps the pressure low so that more energy can be taken out in the turbine. Making steam by burning fuel is the boiler's job, raising water pressure is the feed pump's job, and further heating steam is the superheater's job.

Q5 | Thermal efficiency

A thermal power plant runs at 200 MW for one hour and uses 40 t of fuel with a heating value of 44,000 kJ/kg. What is its approximate thermal efficiency?

  1. 11.4%
  2. 40.9%
  3. 59.1%
  4. 244.4%
AnswerB. 40.9%

Electrical energy = 200,000 kW × 1 h = 200,000 kWh; since 1 kWh = 3,600 kJ, that is 7.2 × 10⁸ kJ. Fuel heat = 40,000 kg × 44,000 kJ/kg = 1.76 × 10⁹ kJ. η = 7.2 × 10⁸ ÷ 1.76 × 10⁹ ≈ 0.409, about 40.9%. 59.1% is the share of losses (100 − 40.9), 11.4% wrongly takes 1 kWh as 1,000 kJ, and 244.4% divides in the wrong order (fuel heat ÷ electrical energy = 1.76 × 10⁹ ÷ 7.2 × 10⁸); efficiency can never exceed 100%.

Q6 | Combined-cycle generation

Which statement correctly describes combined-cycle power generation (コンバインドサイクル発電)?

  1. Steam is made from the heat of gas-turbine exhaust and a steam turbine is also driven
  2. A diesel engine generates power and its exhaust is released directly to the air
  3. Steam made in a nuclear reactor is sent to a gas turbine to generate power
  4. Solar and wind power are installed on the same site to generate power
AnswerA. Steam is made from the heat of gas-turbine exhaust and a steam turbine is also driven

In combined-cycle generation, the hot exhaust from the gas turbine produces steam in a heat-recovery boiler, which drives a steam turbine as well, giving high thermal efficiency. A diesel engine is internal-combustion generation, reactor steam drives a steam turbine in nuclear generation, and co-locating solar and wind is simply a mix of renewables; none of these is combined cycle.

Q7 | Boiling water reactor

Which is a feature of the boiling water reactor (BWR, 沸騰水型), a type of light water reactor?

  1. High-temperature, high-pressure water from the reactor goes to a steam generator, which boils water in a separate loop
  2. It makes steam using the heat of nuclear fusion rather than fission
  3. Steam is produced inside the reactor and sent to the turbine
  4. It takes electricity directly from reactor heat, so no turbine is used
AnswerC. Steam is produced inside the reactor and sent to the turbine

A BWR boils water inside the reactor and sends that steam to the turbine. Using a steam generator to boil water in a separate loop is the pressurised water reactor (PWR, 加圧水型). Present nuclear plants use fission heat, not fusion, and both types drive turbines with steam.

Q8 | Wind power output

In wind power generation, if the wind speed doubles, by what factor does the theoretically available output change (other conditions unchanged)?

  1. 2 times
  2. 4 times
  3. 6 times
  4. 8 times
AnswerD. 8 times

Wind power is proportional to the cube of the wind speed, so 2³ = 8 times. 2 times assumes proportionality to speed, 4 times assumes the square (looking only at ½mv² and forgetting that the mass of air passing each second also grows with speed), and 6 times mistakes 2³ for 2 × 3 (treating the power as multiplication).

Q9 | Fuel cells

Which statement correctly describes fuel-cell power generation (燃料電池)?

  1. Heat from burning fuel makes steam that turns a turbine to produce AC
  2. Electricity (DC) is taken directly from the reaction of hydrogen and oxygen, which produces water
  3. Light striking a semiconductor directly produces AC electricity
  4. It only stores charged electricity and discharges it when needed, using no fuel
AnswerB. Electricity (DC) is taken directly from the reaction of hydrogen and oxygen, which produces water

A fuel cell takes DC electricity directly from the chemical reaction of hydrogen and oxygen, and the product is water. Burning fuel to turn a turbine is thermal power, converting light is a solar cell (which gives DC), and only storing and releasing electricity is a storage battery, not a fuel cell.

Q10 | Speed of a synchronous generator

What is the speed of a 4-pole synchronous generator at 60 Hz?

  1. 3,600 min⁻¹
  2. 1,800 min⁻¹
  3. 1,500 min⁻¹
  4. 900 min⁻¹
AnswerB. 1,800 min⁻¹

N = 120f ÷ p = 120 × 60 ÷ 4 = 1,800 min⁻¹. 3,600 min⁻¹ is for 2 poles, 900 min⁻¹ is for 8 poles, and 1,500 min⁻¹ uses 50 Hz.

Q11 | Transmission voltage and losses

On a three-phase three-wire line sending the same power at the same power factor, by what factor do the line losses change if the transmission voltage is doubled (same conductors)?

  1. 1/8
  2. 1/4
  3. 1/2
  4. No change
AnswerB. 1/4

Doubling the voltage halves the current, and the loss 3I²r is proportional to the square of the current, so (1/2)² = 1/4. 1/2 assumes loss proportional to current, 1/8 assumes the cube, and 'no change' overlooks that the current falls.

Q12 | Overhead ground wire

What is the main role of the overhead ground wire (架空地線) on an overhead transmission line?

  1. Suppressing conductor vibration to prevent breakage
  2. Moving the arc away from the insulators during flashover
  3. Shielding the line from direct lightning strikes
  4. Reducing corona by using several conductors per phase
AnswerC. Shielding the line from direct lightning strikes

The overhead ground wire is an earthed wire strung above the conductors to keep lightning from striking them directly (shielding). Suppressing vibration is the damper's job, moving the arc away from insulators is the arcing horn's job, and reducing corona is the role of bundled conductors.

Q13 | Arcing horns

Which correctly describes the role of arcing horns (アークホーン) fitted to transmission-line insulators?

  1. During a flashover from lightning, they move the arc away from the insulator to prevent damage
  2. They absorb wind-induced conductor vibration to prevent fatigue
  3. They lower the line voltage to a level customers can use
  4. They convert the line current to a size that meters can measure
AnswerA. During a flashover from lightning, they move the arc away from the insulator to prevent damage

Arcing horns are metal fittings at both ends of an insulator string that move the flashover arc off the insulator surface so the insulator is not destroyed by heat. Absorbing vibration is the damper's job, lowering voltage is the transformer's job, and converting current for meters is the current transformer's job.

Q14 | Dampers

What is the purpose of dampers fitted to overhead transmission lines?

  1. Cooling the conductors to increase transmission capacity
  2. Carrying lightning current to earth
  3. Keeping a fixed spacing between conductors
  4. Suppressing wind-induced vibration to prevent conductor damage
AnswerD. Suppressing wind-induced vibration to prevent conductor damage

Dampers are weights attached to the conductor that suppress wind-induced vibration and prevent strand breakage near the support points. Carrying lightning current to earth is done by the ground wire and earthing, keeping conductor spacing is the spacer's job, and dampers do not cool the conductor.

Q15 | Loss on a three-phase line

A three-phase three-wire line supplies a 1,000 kW load at a line voltage of 6.6 kV and a power factor of 0.8. If each conductor has a resistance of 0.5 Ω, what is the approximate line loss?

  1. 17.9 kW
  2. 12.0 kW
  3. 11.5 kW
  4. 6.0 kW
AnswerA. 17.9 kW

I = P ÷ (√3 × V × cosθ) = 1,000 ÷ (√3 × 6.6 × 0.8) ≈ 109.3 A. Loss = 3 × I² × r = 3 × 109.3² × 0.5 ≈ 17,900 W ≈ 17.9 kW. 6.0 kW counts only one conductor, 12.0 kW counts two conductors as for single-phase two-wire, and 11.5 kW leaves out the power factor (current 87.5 A).

Q16 | Voltage drop on a three-phase line

On a three-phase three-wire line, the line current is 100 A, each conductor has resistance 0.4 Ω and reactance 0.3 Ω, and the load power factor is 0.8 lagging. Using the approximate formula, what is the voltage drop?

  1. 121 V
  2. 87 V
  3. 83 V
  4. 50 V
AnswerB. 87 V

e = √3 × I × (r cosθ + x sinθ). sinθ = √(1 − 0.8²) = 0.6, so e = √3 × 100 × (0.4 × 0.8 + 0.3 × 0.6) = √3 × 100 × 0.5 ≈ 86.6 V, about 87 V. 50 V forgets the √3, 83 V swaps cosθ and sinθ, and 121 V simply adds r and x (√3 × 100 × 0.7).

Q17 | Gas-insulated switchgear

Which correctly describes gas-insulated switchgear (GIS, ガス絶縁開閉装置) in substations?

  1. Switchgear with live parts exposed in air for easy inspection
  2. Switchgear that extinguishes the arc in insulating oil
  3. A circuit breaker that interrupts current in a vacuum chamber
  4. Compact switchgear with live parts enclosed in metal and insulated with SF₆ gas
AnswerD. Compact switchgear with live parts enclosed in metal and insulated with SF₆ gas

GIS encloses circuit breakers, disconnectors, busbars and so on in earthed metal enclosures insulated with highly insulating SF₆ (sulfur hexafluoride) gas, making the equipment compact for urban substations. Live parts exposed in air is air insulation, extinguishing the arc in oil is an oil circuit breaker, and interrupting in a vacuum is a vacuum circuit breaker; none of these describes GIS.

Q18 | Where arresters are required

Under the Interpretation of Technical Standards for Electrical Equipment (電気設備の技術基準の解釈), where must a surge arrester be installed (at or near the point)?

  1. At the lead-in and lead-out of overhead lines at power stations and substations
  2. At the start of branch circuits of low-voltage indoor wiring
  3. At the service entrance of every low-voltage customer
  4. At the receiving point of a customer supplied only by underground lines
AnswerA. At the lead-in and lead-out of overhead lines at power stations and substations

Article 37(1) requires arresters on high-voltage and extra-high-voltage circuits at the lead-in (excluding customers' lead-ins) and lead-out of overhead lines at power stations, storage stations, substations and similar places. Because it covers high and extra-high voltage circuits, low-voltage branch circuits and low-voltage customers' service entrances are not included, and the listed points relate to overhead lines, not supply by underground lines only.

Q19 | Shunt reactors

Which phase-modifying equipment in a substation is used to keep the system voltage from rising too high at light load, such as late at night?

  1. Power capacitor
  2. Shunt reactor
  3. Voltage transformer (for instruments)
  4. Surge arrester
AnswerB. Shunt reactor

At light load the line capacitance tends to raise the voltage, so a shunt reactor (分路リアクトル) absorbs leading reactive power to hold the voltage down. A power capacitor supplies lagging reactive power at heavy load to stop the voltage falling, and would raise the voltage further at light load. An instrument voltage transformer steps voltage down for measurement and an arrester protects against overvoltages; neither is phase-modifying equipment.

Q20 | Fence for an extra-high-voltage substation

An outdoor substation has live parts at 66,000 V. Under the Interpretation of Technical Standards for Electrical Equipment, what must the fence height plus the distance from the fence to the live parts be at least?

  1. 3 m
  2. 4 m
  3. 5 m
  4. 6 m
AnswerD. 6 m

Article 38 (Table 38-1) requires the fence height plus the distance from the fence to live parts to be at least 6 m when the voltage is over 35,000 V and up to 160,000 V; 66,000 V falls in this range. 5 m is the value for 35,000 V or less, and 3 m and 4 m are not in the table.

Q21 | Horizontal illuminance

A light source of 1,000 cd (equal in all directions) is 3 m above the floor. What is the horizontal illuminance at a floor point 4 m horizontally from the point directly below the source?

  1. 24 lx
  2. 32 lx
  3. 40 lx
  4. 111 lx
AnswerA. 24 lx

The distance to the point is r = √(3² + 4²) = 5 m, and cosθ = 3 ÷ 5 = 0.6. Eh = (1,000 ÷ 5²) × 0.6 = 40 × 0.6 = 24 lx. 40 lx is the illuminance on a surface facing the light (cosθ forgotten), 32 lx wrongly uses cosθ = 4 ÷ 5, and 111 lx uses only the 3 m height, giving the illuminance directly below.

Q22 | Lumen method

An office of 200 m² floor area should have an average illuminance of 500 lx. Each luminaire gives 5,000 lm, the utilisation factor is 0.6 and the maintenance factor is 0.7. What is the minimum number of luminaires?

  1. 48
  2. 34
  3. 29
  4. 20
AnswerA. 48

N = E × A ÷ (F × U × M) = 500 × 200 ÷ (5,000 × 0.6 × 0.7) = 100,000 ÷ 2,100 ≈ 47.6, rounded up to 48. 34 forgets the maintenance factor (33.3), 29 forgets the utilisation factor (28.6), and 20 forgets both.

Q23 | Flux of a uniform point source

What is the approximate total luminous flux of a point source with a luminous intensity of 100 cd in every direction (a uniform point source)?

  1. 1,257 lm
  2. 628 lm
  3. 314 lm
  4. 8 lm
AnswerA. 1,257 lm

Total flux is the intensity times the solid angle of a whole sphere, 4π sr: F = 4πI = 4 × 3.14 × 100 ≈ 1,257 lm. 628 lm uses 2π (a hemisphere), 314 lm uses π, and 8 lm divides 100 by 4π instead of multiplying.

Q24 | Time to heat water

20 L of water is heated from 15 °C to 85 °C with a 2 kW heater of 80% efficiency. About how many minutes does it take? Take 1 L of water as 1 kg and its specific heat as 4.2 kJ/(kg·K).

  1. 39 min
  2. 49 min
  3. 61 min
  4. 77 min
AnswerC. 61 min

Heat needed = 20 × 4.2 × (85 − 15) = 5,880 kJ. With 80% efficiency the heater must supply 5,880 ÷ 0.8 = 7,350 kJ. 2 kW = 2 kJ/s, so 7,350 ÷ 2 = 3,675 s ≈ 61 min. 49 min ignores the efficiency, 39 min multiplies by the efficiency instead of dividing, and 77 min divides by the efficiency twice.

Q25 | Induction heating

Which correctly describes induction heating (誘導加熱)?

  1. Heating by dielectric loss inside an insulating material in a high-frequency electric field
  2. Heating by the Joule heat of eddy currents induced in metal by an alternating magnetic field
  3. Heating by the high temperature of an arc between electrodes
  4. Heating by shining infrared rays onto the surface of an object
AnswerB. Heating by the Joule heat of eddy currents induced in metal by an alternating magnetic field

Induction heating uses the alternating magnetic field of a coil to induce eddy currents in a metal (conductive object) and heats it with their Joule heat; it is used in IH cookers. Heating an insulator by dielectric loss is dielectric heating, heating with an arc is arc heating, and shining infrared rays is infrared heating.

Q26 | Dielectric heating

Which heating method, used in microwave ovens, heats an insulating material (dielectric) from the inside?

  1. Resistance heating
  2. Induction heating
  3. Arc heating
  4. Dielectric heating
AnswerD. Dielectric heating

Dielectric heating (誘電加熱) heats an object from the inside by the dielectric loss that arises in an insulator in a high-frequency electric field (microwaves in a microwave oven). Resistance heating uses Joule heat from current, induction heating uses eddy currents in metal, and arc heating uses the heat of an arc; none heats an insulator from inside.

Q27 | Coefficient of performance

A heat-pump water heater with a coefficient of performance (COP) of 4.0 runs for one hour at 1.2 kW input. How much heat does it deliver?

  1. 4.8 kJ
  2. 1,080 kJ
  3. 4,320 kJ
  4. 17,280 kJ
AnswerD. 17,280 kJ

Heat output = 1.2 kW × 4.0 = 4.8 kW, i.e. 4.8 kWh in one hour; with 1 kWh = 3,600 kJ that is 17,280 kJ. 4,320 kJ converts only the electrical input (1.2 kWh) and forgets the COP, 1,080 kJ divides by the COP, and 4.8 kJ forgets the 3,600 kJ/kWh conversion.

Q28 | Motor output for a pump

A pump delivers 1.2 m³/min against a total head of 25 m. With a pump efficiency of 75% and a margin factor of 1.1, what is the approximate motor output required?

  1. 4.9 kW
  2. 6.5 kW
  3. 7.2 kW
  4. 431 kW
AnswerC. 7.2 kW

Q = 1.2 ÷ 60 = 0.02 m³/s. P = 9.8 × Q × H × K ÷ η = 9.8 × 0.02 × 25 × 1.1 ÷ 0.75 ≈ 7.19 kW, about 7.2 kW. 6.5 kW forgets the margin factor, 4.9 kW forgets both the margin factor and the efficiency, and 431 kW does not divide m³/min by 60.

Q29 | Motor output for a hoist

A hoist lifts a 1.5 t load at 30 m per minute. If the hoist efficiency is 70%, what is the approximate motor output required?

  1. 5.1 kW
  2. 7.4 kW
  3. 10.5 kW
  4. 630 kW
AnswerC. 10.5 kW

v = 30 ÷ 60 = 0.5 m/s. P = 9.8 × m × v ÷ η = 9.8 × 1.5 × 0.5 ÷ 0.7 = 10.5 kW. 7.4 kW forgets the efficiency (7.35), 5.1 kW multiplies by the efficiency instead of dividing, and 630 kW does not divide m/min by 60.

Q30 | Motor torque

A motor runs at an output of 15 kW and a speed of 1,450 min⁻¹. What is the approximate shaft torque?

  1. 0.099 N·m
  2. 10.3 N·m
  3. 98.8 N·m
  4. 621 N·m
AnswerC. 98.8 N·m

From P = 2π × (n ÷ 60) × T, T = 60P ÷ (2πn) = 60 × 15,000 ÷ (2 × 3.14 × 1,450) ≈ 98.8 N·m. 621 N·m forgets to divide by 2π, 10.3 N·m just divides power by speed, and 0.099 N·m leaves the power in kW (15).

Practice: answer the questions on this page

This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.

* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.

This page is a translation of the Japanese original. If the translation and the original differ, the Japanese version takes precedence. This translation was made with AI and may contain errors. Report a translation error View the Japanese original