Karinoya Learning Room

Qualifications · Electrician Class 2 & Class 1 (Written Exam) Lab

Wiring Diagrams 3: Integrated Questions

Read the questions and explanations in English. The lectures (explanatory articles) are available in Japanese only.

View the Japanese version (with lectures) →

Q1 | Minimum wires in ③
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the minimum number of wires (cores) in section ③ (from joint box J1 to the 3-way switch a in the hallway)?

  1. 2
  2. 3
  3. 4
  4. 5
AnswerB. 3

Lamp a is switched from two places with 3-way switches (② and ③). The live (non-earthed) wire goes to the common terminal of the living-room switch, so the hallway switch needs the two travellers plus the wire from its common terminal back to lamp a: 3 wires. Two is not enough for the travellers; 4 or 5 wrongly adds the circuit of switch b, which is wired separately by cable ⑤.

Q2 | Cable for ②
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, which cable is most appropriate for section ② (from J1 to the 3-way switch a in the living room)? (The notes say indoor wiring uses VVF1.6.)

  1. VVF1.6-2C
  2. VVF2.0-2C
  3. VVF2.0-3C
  4. VVF1.6-3C
AnswerD. VVF1.6-3C

The live wire comes to the common terminal of the living-room 3-way switch, and two travellers leave from terminals 1 and 3. Section ② needs 3 wires, so the cable is VVF1.6-3C (1.6 mm, 3 cores). A 2C cable has only 2 cores. The notes use 2.0 mm only for the 200 V circuit ⑦; this lighting circuit is 1.6 mm.

Q3 | Minimum wires in ⑥
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the minimum number of wires (cores) in section ⑥ (from J1 to J2)?

  1. 2
  2. 3
  3. 4
  4. 5
AnswerA. 2

Section ⑥ only carries the supply for lamp b, switch b and the indicator lamp. Sending one live and one earthed (neutral) wire to J2 is enough, because J2 splits them to the switch group (⑤) and lamp b: 2 wires. The travellers for lamp a go directly to the hallway switch via ③, so they are not in ⑥. Three or more wrongly counts wires of lamp a or the switched return.

Q4 | Minimum wires in ⑤ (indicator lamp)
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the minimum number of wires (cores) in section ⑤ (from J2 to switch b and the indicator lamp in the hallway)? The indicator lamp lights while lamp b is on.

  1. 2
  2. 4
  3. 3
  4. 5
AnswerC. 3

Switch b needs one live wire and one switched return to lamp b. The indicator lamp is connected in parallel with lamp b, so it also needs an earthed (neutral) wire: 3 wires in total. Two would be a switch without the indicator lamp. Four or five wrongly adds the wires of 3-way switch a, which arrive separately through ③.

Q5 | Wires with a locator-lamp switch
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, the separate indicator lamp is removed and switch b is replaced with a switch that has a built-in locator lamp (marked H; it glows while lamp b is off). What is the minimum number of wires (cores) in ⑤?

  1. 3
  2. 4
  3. 2
  4. 1
AnswerC. 2

A locator lamp is connected across the switch contacts; while the switch is off, a small current flows through lamp b and makes it glow. No earthed (neutral) wire is needed at the switch, so ⑤ needs only the live wire and the switched return: 2 wires. Three is the count for an indicator lamp in parallel with the load; four has no basis; one wire cannot form a switch circuit.

Q6 | Connections inside J1
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the minimum number of connection points (where wires are joined) inside joint box J1?

  1. 5
  2. 4
  3. 6
  4. 3
AnswerA. 5

Wires entering J1: ① (live, earthed), lamp a (earthed, return), ② (common, two travellers), ③ (two travellers, return) and ⑥ (live, earthed). The connections are: live (①, common of ②, ⑥), earthed (①, lamp a, ⑥), traveller 1, traveller 2, and the return (common of ③ to lamp a): 5 points. Three or four misses the traveller or return joints; six counts a joint twice.

Q7 | Ring sleeve size and mark
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, ring sleeves (E type) are used at the three points in J1 where two 1.6 mm wires are joined. Which combination of sleeve size and crimp mark is correct?

  1. Small sleeve, mark "小 (small)"
  2. Medium sleeve, mark "○"
  3. Medium sleeve, mark "中 (medium)"
  4. Small sleeve, mark "○"
AnswerD. Small sleeve, mark "○"

In the ring-sleeve table published by the examination centre (based on JIS C 2806), two 1.6 mm wires use a small sleeve with the crimp mark "○". Marks are fixed for each combination in the table, and "小" does not apply to this one. Medium sleeves are for more or thicker wires; on two 1.6 mm wires they are too large to crimp firmly.

Q8 | Ring sleeve crimping tool
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, which tool is correct for making the connections in J1 with ring sleeves?

  1. A crimping tool for crimp terminals with red handles
  2. A ring-sleeve crimping tool with yellow handles
  3. Pliers
  4. A wire stripper
AnswerB. A ring-sleeve crimping tool with yellow handles

Ring sleeves are crimped with a ring-sleeve crimping tool complying with JIS, which has yellow handles (examination centre sample question and skills-test notes). A tool with red handles is for crimp terminals and must not be used on ring sleeves. Pliers cut and bend wire and cannot apply the specified crimping force. A wire stripper removes insulation.

Q9 | Push-in connectors needed
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, all connections inside J1 are made with push-in connectors. Which set of connectors is needed?

  1. Five 2-wire connectors
  2. Three 2-wire and two 3-wire connectors
  3. Two 2-wire and three 3-wire connectors
  4. Five 3-wire connectors
AnswerB. Three 2-wire and two 3-wire connectors

J1 has 5 connection points. The live joint (①, ②, ⑥) and the earthed joint (①, lamp a, ⑥) each join 3 wires, so they need 3-wire connectors; the two traveller joints and the return joint join 2 wires each, so they need 2-wire connectors. That is three 2-wire and two 3-wire connectors. Two-wire connectors alone cannot join 3 wires; using 3-wire connectors for 2-wire joints does not match the joint.

Q10 | Improper joint in a box
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, which practice for the connections inside J1 is improper?

  1. The conductor was pushed fully into the push-in connector and was visible at its tip.
  2. After crimping, the mark on the ring sleeve was checked.
  3. All the joints were kept inside the joint box.
  4. The ring sleeve was crimped over the wire insulation.
AnswerD. The ring sleeve was crimped over the wire insulation.

Crimping over the insulation does not give firm metal-to-metal contact, so the joint resistance rises and it can overheat; the examination centre treats this as a defect. For push-in connectors, pushing the conductor fully in so it is visible at the tip is correct. Checking the crimp mark after crimping is the correct procedure. In cable work, joints are made inside a box.

Q11 | Tool for stripping VVF sheath
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, which tool is most suitable for removing the sheath and insulation of the VVF cables in ① to ⑥?

  1. A VVF stripper
  2. A ring-sleeve crimping tool
  3. A pipe cutter
  4. A knockout punch
AnswerA. A VVF stripper

A VVF stripper removes the sheath and insulation of VVF cable without nicking the conductor. A ring-sleeve crimping tool is for joints, not stripping. A pipe cutter cuts conduit, and a knockout punch makes holes in metal boxes for conduit.

Q12 | Mounting several switches
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In the hallway in Figure 1, 3-way switch a, switch b and the indicator lamp are flush-mounted together in one place on the wall. Which combination of materials is most appropriate?

  1. A VVF joint box and a rubber grommet
  2. A normal bend and a coupling
  3. A flush switch box and a multi-gang mounting frame
  4. A locknut and an insulating bushing
AnswerC. A flush switch box and a multi-gang mounting frame

Flush switches and indicator lamps are mounted side by side on a multi-gang mounting frame, which is fixed to a switch box in the wall. A VVF joint box is for joining wires, not for mounting devices. Normal bends and couplings bend and join conduit; locknuts and insulating bushings fix conduit to boxes and protect the wires.

Q13 | Meaning of VVF2.0-2C
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In the notes of Figure 1, what does "VVF2.0-2C" for ⑦ mean?

  1. VVF cable with 2.0 mm² conductors and 2 cores
  2. Two cables with 2.0 mm diameter conductors
  3. VVF cable with 2.0 mm diameter conductors and 2 cores
  4. VVF cable rated 20 A with 2 cores
AnswerC. VVF cable with 2.0 mm diameter conductors and 2 cores

VVF is 600 V vinyl-insulated vinyl-sheathed flat cable. "2.0" is the diameter (mm) of the solid conductor and "2C" is the number of cores (2). Cross-sectional area (mm²) is how stranded conductors are sized, so reading 2.0 as an area is wrong. "2C" is not the number of cables. Allowable current is not written in the cable code; it depends on the size and other factors.

Q14 | Meaning of "20A250V"
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what does "20A250V" written beside receptacle ⑦ indicate?

  1. The receptacle's rated current 20 A and rated voltage 250 V
  2. The branch breaker's rating of 20 A, 250 V
  3. The air conditioner's power use of 20 A × 250 V
  4. The cable's allowable current 20 A and insulation withstand voltage 250 V
AnswerA. The receptacle's rated current 20 A and rated voltage 250 V

Under JIS C 0303, a receptacle symbol is annotated with its rated current when it is 20 A or more, and with its rated voltage when it is 250 V or more. "20A250V" is the rating of the receptacle itself. It does not show the breaker rating (shown at the panel), the air conditioner's power, or the cable's performance.

Q15 | Rating of an unmarked receptacle
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, receptacle ⑧ is marked only "2-gang". Which description of it is correct?

  1. A 2-gang receptacle rated 20 A, 125 V
  2. A 2-gang receptacle rated 15 A, 250 V
  3. One 15 A, 125 V receptacle at each of two places
  4. A 2-gang receptacle rated 15 A, 125 V
AnswerD. A 2-gang receptacle rated 15 A, 125 V

Under JIS C 0303, 15 A receptacles carry no current annotation; the current is annotated only at 20 A or more. The voltage is annotated only at 250 V or more, so an unmarked receptacle is the ordinary 15 A, 125 V type. The number of outlets is annotated when there are 2 or more, so "2-gang" means one device with two sockets, not two devices in different places.

Q16 | Earthing class for ⑦
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, which class of earthing is applied to the earth pole of receptacle ⑦ (single-phase 200 V, for an air conditioner)?

  1. Class A earthing
  2. Class D earthing
  3. Class B earthing
  4. Class C earthing
AnswerB. Class D earthing

Equipment on low voltage of 300 V or less uses Class D earthing (the examination centre's sample question also treats the earth pole of a receptacle on a circuit of 300 V or less as Class D). ⑦ is 200 V, so Class D. Class A is for high-voltage equipment, Class B for the low-voltage side of transformers (such as the neutral), and Class C for low-voltage equipment above 300 V.

Q17 | Insulation resistance of ⑦
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the minimum insulation resistance between the circuit and earth for circuit ⑦ (a 200 V circuit taken from the single-phase 3-wire 100/200 V supply)?

  1. 0.2 MΩ
  2. 0.1 MΩ
  3. 0.4 MΩ
  4. 1 MΩ
AnswerB. 0.1 MΩ

Under Article 58 of the ministerial ordinance, a circuit of 300 V or less with a voltage to earth of 150 V or less needs at least 0.1 MΩ. A 200 V circuit from a single-phase 3-wire 100/200 V supply has 200 V between wires but only 100 V from each wire to earth, so 0.1 MΩ applies. 0.2 MΩ is for circuits of 300 V or less with more than 150 V to earth (such as 3-phase 200 V); 0.4 MΩ is for circuits above 300 V; 1 MΩ is not in the ordinance table.

Q18 | Preparing an insulation test
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

In Figure 1, what is the most appropriate preparation for measuring the insulation resistance between the wires of the receptacle circuit ⑧?

  1. Keep the branch breaker on and unplug all appliances.
  2. Turn off the branch breaker and leave the appliances plugged in.
  3. Turn off the branch breaker and measure between the earth pole and earth.
  4. Turn off the branch breaker and unplug all appliances from the receptacle.
AnswerD. Turn off the branch breaker and unplug all appliances from the receptacle.

Insulation resistance is measured with the power off. When measuring between wires, connected appliances would be measured through their internal circuits, hiding the wiring's insulation. Measuring with the breaker on applies the tester's voltage to a live circuit, which is dangerous and gives wrong readings. Measuring between the earth pole and earth is an earth-resistance test, not wire-to-wire insulation.

Q19 | The last inspection step
Living roomKitchenHallwayPanelaa32163J1J2a3bIndicator lamp (separate)5bReceptacle 2-gang8Receptacle20A250V, earthed7Notes1. Unless noted, indoor wiring is cable work using VVF1.6 cable.2. Supply: single-phase 3-wire 100/200 V. ⑦ is a 200 V air-conditioner outlet (VVF2.0-2C).3. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.4. J1, J2: joint boxes for VVF. Devices are named in text instead of symbols.
Figure 1. Wiring diagram of part of a wooden house (original diagram for this lab)

After the work in Figure 1 is finished, which inspection is normally done last?

  1. Energised test
  2. Visual inspection
  3. Insulation resistance measurement
  4. Earth resistance measurement
AnswerA. Energised test

Before switching on, the work is visually inspected and the insulation and earth resistances are measured to make sure there is no leakage or earthing fault. Only after safety is confirmed is power applied, last, to check lamps, switches and receptacle voltage. Visual inspection comes first, and insulation and earth resistance are measured before energising.

Q20 | Finishing the inside of conduit ⑩
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, after cutting the conduit for ⑩, which tool smooths the inside edge (burr) of the cut?

  1. A pipe bender
  2. A pipe threader
  3. A reamer
  4. A knockout punch
AnswerC. A reamer

A reamer trims the inside of the cut end of a metal conduit so that wire insulation is not damaged when pulled in (examination centre sample explanation). A pipe bender bends conduit; a threader cuts threads on the pipe end and is not used on threadless conduit; a knockout punch makes holes in metal boxes.

Q21 | Bending conduit ⑩
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which tool is used to bend the steel conduit of ⑩ at a right angle near the motor?

  1. A blow torch
  2. A reamer
  3. A pipe bender
  4. A pipe vice
AnswerC. A pipe bender

Steel conduit is bent with a pipe bender (examination centre sample question). A blow torch is used, for example, to heat rigid PVC conduit for bending, not for steel conduit. A reamer finishes the inside of a cut; a pipe vice holds the pipe while cutting.

Q22 | Material at the end of conduit ⑩
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which material is fitted to the end of the conduit for ⑩ to stop the wire insulation being damaged by the cut edge?

  1. An insulating bushing
  2. A coupling
  3. A normal bend
  4. A saddle
AnswerA. An insulating bushing

An insulating bushing is fitted on the conduit end to protect the insulation where wires enter and leave. A coupling joins two conduits, a normal bend is a ready-made right-angle bend, and a saddle fixes the conduit to a wall or ceiling.

Q23 | Pulling wires into conduit
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which tool is used to pull three IV2.0 wires into the conduit of ⑩?

  1. A brace (click-ball)
  2. A wire stripper
  3. A pipe vice
  4. A fish tape (wire puller)
AnswerD. A fish tape (wire puller)

A fish tape is pushed through the conduit first; the wires are tied to its end and pulled in. A brace (click-ball) turns a reamer or bit by hand, a wire stripper removes insulation, and a pipe vice holds pipe; none of them pulls wires.

Q24 | Improper work on ⑩
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which practice for ⑩ (exposed metal-conduit work using threadless steel conduit) is improper?

  1. Threadless box connectors were used to connect the conduit to boxes.
  2. Wires were joined inside the conduit.
  3. The conduit was fixed to the building with saddles.
  4. IV2.0 insulated wire was used.
AnswerB. Wires were joined inside the conduit.

In metal-conduit work, wires must not be joined inside the conduit; joints there cannot be inspected and may be damaged when pulling, so joints are made in boxes. Threadless conduit is connected to boxes with threadless box connectors and fixed with saddles. Insulated wire such as IV is pulled into the conduit.

Q25 | Maximum earth resistance at ⑪
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which combination gives the earthing class and the maximum allowed earth resistance for ⑪ (earthing of the metal frame of the 3-phase 200 V motor)?

  1. Class D, 100 Ω
  2. Class D, 500 Ω
  3. Class C, 10 Ω
  4. Class C, 500 Ω
AnswerB. Class D, 500 Ω

200 V is 300 V or less, so Class D earthing applies. Class D is 100 Ω or less in principle, but 500 Ω or less is allowed when a device automatically disconnects the circuit within 0.5 s on an earth fault (Interpretation (解釈) Art. 17(4)); note 4 says RCDs with an operating time of 0.1 s or less are installed, so the maximum is 500 Ω (the same reasoning as the examination centre sample). 100 Ω is the value without such a device. Class C is for low-voltage equipment above 300 V and does not apply to this motor.

Q26 | Insulation resistance of ⑩
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, what is the minimum insulation resistance between the circuit and earth for the motor circuit ⑩ (3-phase 3-wire 200 V)?

  1. 0.1 MΩ
  2. 0.4 MΩ
  3. 0.3 MΩ
  4. 0.2 MΩ
AnswerD. 0.2 MΩ

Under Article 58 of the ministerial ordinance, for circuits of 300 V or less the minimum is 0.1 MΩ when the voltage to earth is 150 V or less and 0.2 MΩ otherwise; circuits above 300 V need 0.4 MΩ. A 3-phase 3-wire 200 V circuit has more than 150 V to earth, so 0.2 MΩ. 0.1 MΩ is for 100 V circuits or the 200 V side of a single-phase 3-wire supply, 0.4 MΩ is for above 300 V, and 0.3 MΩ is not in the table.

Q27 | Measuring earth resistance
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which description of measuring the earth resistance of ⑪ with an earth resistance tester is correct?

  1. Drive two auxiliary electrodes away from the electrode under test and connect all three to measure.
  2. Use no auxiliary electrodes; measure between the electrode and the motor frame.
  3. Drive the auxiliary electrodes right next to (a few cm from) the electrode under test.
  4. Use the highest range of an insulation tester between the earth wire and earth.
AnswerA. Drive two auxiliary electrodes away from the electrode under test and connect all three to measure.

An earth resistance tester uses the electrode under test (E) plus two auxiliary electrodes (P and C) driven at a distance, all three connected. Measuring between the frame and the electrode only measures the connecting conductor, not the resistance to earth. If the auxiliary electrodes are too close, the soil regions around the electrodes overlap and the reading is wrong. An insulation tester measures insulation, not earth resistance.

Q28 | Checking phase sequence
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which instrument is used to check the phase sequence of the supply before first running the 3-phase 200 V motor?

  1. A light meter
  2. An earth resistance tester
  3. A phase-sequence indicator
  4. An insulation tester
AnswerC. A phase-sequence indicator

The rotation direction of a 3-phase induction motor depends on the phase sequence, so a phase-sequence indicator is used. A light meter measures brightness, an earth resistance tester measures the resistance between an electrode and earth, and an insulation tester measures circuit insulation; none shows phase sequence.

Q29 | Correcting reverse rotation
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, the 3-phase 200 V motor runs in the wrong direction during a test run. What is the correct fix?

  1. Shift all three wires by one position, keeping their order.
  2. Run the motor with the earth wire ⑪ disconnected.
  3. Swap any two of the three supply wires.
  4. Replace the RCD with one of higher rated sensitivity current.
AnswerC. Swap any two of the three supply wires.

Swapping any two of the three wires reverses the phase sequence and the rotation. Shifting all three by one position keeps the same sequence, so the direction does not change. Removing the earth wire is dangerous and unrelated to direction; the RCD sensitivity is also unrelated.

Q30 | Measuring running current
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which instrument measures the current in one wire of circuit ⑩ while the motor is running, without breaking the circuit?

  1. A clamp meter
  2. A circuit tester (multimeter)
  3. A voltage detector
  4. An insulation tester
AnswerA. A clamp meter

A clamp meter measures current just by clamping around a wire, without breaking the circuit. A circuit tester must be connected in series by breaking the circuit, which is unsuitable for a running power circuit. A voltage detector only checks whether a conductor is live, and an insulation tester measures insulation on a de-energised circuit.

Q31 | Leakage on a live circuit
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, lighting circuit ⑫ cannot be switched off. Which method correctly checks whether there is leakage current?

  1. Clamp only one wire with a clamp-type leakage current meter.
  2. Measure between the wires on the AC voltage range of a circuit tester.
  3. Apply an insulation tester between a live wire and earth.
  4. Clamp both wires of the circuit together with a clamp-type leakage current meter.
AnswerD. Clamp both wires of the circuit together with a clamp-type leakage current meter.

When all circuit wires are clamped together, the outgoing and returning currents cancel and only the leakage current remains. The examination centre sample also says leakage current is measured with a clamp-type leakage meter. Clamping one wire measures load current. A circuit tester cannot measure leakage; its AC voltage range only measures voltage. An insulation tester is for de-energised circuits and is dangerous on a live one.

Q32 | Connecting PF conduit to a box
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which material connects the PF conduit of ⑫ to the outlet box OB?

  1. A threadless box connector
  2. A PF conduit box connector
  3. A TS coupling
  4. An entrance cap
AnswerB. A PF conduit box connector

PF (flexible synthetic-resin) conduit is connected to boxes with a PF conduit box connector. A threadless box connector is for threadless steel conduit, a TS coupling joins rigid PVC conduits with adhesive, and an entrance cap is fitted on an outdoor conduit end to keep rain out.

Q33 | Cutting PF conduit
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, which tool is suitable for cutting the PF conduit of ⑫?

  1. A pipe bender
  2. A plastic conduit cutter
  3. A pipe threader
  4. A knockout punch
AnswerB. A plastic conduit cutter

A plastic conduit cutter cuts synthetic-resin conduit such as PF cleanly. A pipe bender bends steel conduit, a threader cuts threads on steel pipe, and a knockout punch makes holes in metal boxes; none of them cuts conduit.

Q34 | Meaning of "A(3A)"
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, what does the switch marked "A(3A)" at outdoor lamp d represent?

  1. A timer switch rated 3 A
  2. A 3 A switch with a built-in indicator lamp
  3. A pull switch rated 3 A
  4. An automatic (photoelectric) switch rated 3 A
AnswerD. An automatic (photoelectric) switch rated 3 A

Under JIS C 0303, an automatic switch used for outdoor lamps is annotated with A and its capacity. It switches on and off automatically according to the surrounding brightness (examination centre sample). A timer switch is marked T, a switch with an indicator lamp L, and a pull switch P.

Q35 | Drilling concrete
Sales floorStoreroomOutdoorsPanelcccOB12PF conduit, IV1.6(embedded in concrete)M3-phase 200 V motorThreadless steel conduit (exposed), IV2.0 x 31011EarthdA(3A)Underground13Notes1. Reinforced-concrete shop. Supply: single-phase 3-wire 100/200 V and 3-phase 3-wire 200 V.2. ⑩ is the 3-phase 200 V motor circuit: three IV2.0 wires in threadless steel conduit.3. ⑫ is a 100 V lighting circuit: IV1.6 wires in PF conduit embedded in concrete.4. RCDs: rated sensitivity current 30 mA, operating time 0.1 s or less.5. OB: outlet box. Devices and wiring methods are named in text instead of symbols.
Figure 2. Wiring diagram of a shop (reinforced concrete; original diagram for this lab)

In Figure 2, a hole for conduit must be made through the reinforced-concrete wall to take wiring ⑬ outdoors. Which tool is suitable?

  1. A hammer drill
  2. A knockout punch
  3. A brace (click-ball)
  4. A wood auger bit
AnswerA. A hammer drill

A hammer drill adds hammering to rotation to drill concrete. A knockout punch is for metal boxes, a brace (click-ball) is turned by hand, and an auger bit drills wood; none is used on concrete.

Practice: answer the questions on this page

This practice tool asks questions in random order (it works when JavaScript is enabled). You can still read all the questions and explanations above without it.

* The explanations are for study purposes. Always check the Electrical Technician Examination Center's official announcements for how the exam is held, its scope and its pass mark. All questions are original questions written for this site, not real exam questions. Real electrical work must follow the law and requires the proper licence.